Inspections for the day of: Monday, August 6, 2012.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00379 INSP-Sprinkler Rough-in8/6/20128/6/20128/6/2012 3:51:18 PMPPASS
Sprinkler piping is ok to cover.
BLD12-01394 FIRE-Final Inspection8/6/20128/6/20128/6/2012 2:23:00 PMPFAIL
No city approved plans on site. Left voice message for Tim. I went over general life safety requirements with Mark, on site.
BLD12-01136 FIRE-Final Inspection8/2/20128/6/20128/6/2012 9:32:43 AMAFAIL
Sprinkler pendants are overspaced for ordinary hazard in the records room as well as spaced at 11' off a wall. Sprinkler pendants are also located too close, under 4", in acouple of other locations. One exit sign and one emergency light failed to function. All of the new door hardware with locks do not open in a single motion. One exterior exit door on the south side of the building needs to be provided with single action hardware and the thumbturn removed or remove all hardware all together and make it a window as discussed. Contractor provided verification of sprinkler monitoring through ADT.