FIR15-00474
| INSP-Final Inspection | 8/5/2015 | 8/6/2015 | 8/7/2015 2:45:42 PM | A | CANC |
|
|
Need ceiling tile for a final
|
MIS15-00196
| FIR-Conference | 7/31/2015 | 8/6/2015 | 8/6/2015 2:49:42 PM | P | DONE |
|
|
Meet at 2PM, Per Tony
|
BLD15-02666
| FIRE-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 1:20:07 PM | A | FAIL |
|
|
See the city approved plans for corrections and their locations. They include the need of a sprinkler monitoring system (per original install drawings there are 164 sprinkler heads), emergency lighting is needed throughout, exit signs provided where shown on the plans, lower fire extinguishers in shop and remove the thumb turn dead bolt from the main exit.
|
BLD15-01603
| FIRE-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 10:33:56 AM | A | FAIL |
|
|
Not really ready for a final yet. I did verify exit signs and emergency lights. I also spoke to plan review about the rear exit door being deleted. Carl Westfall is ok with it and noted it on the city approved electronic plans.
|
FIR15-00415
| INSP-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 10:16:49 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00839
| INSP-Supply line flush | 8/5/2015 | 8/6/2015 | 8/6/2015 10:11:09 AM | A | CANC |
|
|
Mike Phone #: ###-####
|
BLD14-03495
| FIRE-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 10:10:04 AM | A | PART |
|
|
Temporary occupancy for life safety with Romeo's permission until the correct address is posted and the stairs are installed. One exit discharge light repaired while on site.
|
FIR15-00474
| INSP-Sprinkler Rough-in | 8/5/2015 | 8/6/2015 | 8/6/2015 8:26:49 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR15-00254
| INSP-Final Inspection | 8/5/2015 | 8/6/2015 | 8/6/2015 7:59:30 AM | P | CANC |
|
|
Phone #: 2088705073 >> Inspection requested via mobile web by John Siewert Inspection cancelled from web by: Chris Siewert
|