Inspections for the day of: Tuesday, August 6, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02515 Electrical Rough-In8/5/20198/6/20198/6/2019 2:35:15 PMAPASS
Wyane. Phone #: ###-#### Ok cover. Talked to contractor, garage is going to be insulated and sheetrocked.
ELE18-01606 Electrical Rough-In8/6/20198/6/20198/6/2019 2:07:08 PMPPASS
B Building, 1st Floor Breezeway Grid Phone #: ###-#### Inspection requested via web by Stephanie Huston Ok cover. Review notes for ele18-01605 for hardlid support of sheetrock
ELE18-01605 Electrical Rough-In8/6/20198/6/20198/6/2019 2:06:32 PMPPASS
A Building 1st Floor Breezeway grid Phone #: ###-#### Inspection requested via web by Stephanie Huston Ok cover area listed. Electrician reviewed cut sheets supplied by sheetrock installer. Hardlid wire supports placed in areas needed to hold the weight of 2 layers of sheetrock.
ELE19-02927 Electrical Rough-In8/6/20198/6/20198/6/2019 2:04:50 PMPPASS
Underground pipe for service extension Phone #: ###-#### Inspection requested via web by Calvin Bohrer Ok cover conduit garage to house.
ELE19-02572 Electrical Rough-In8/5/20198/6/20198/6/2019 12:16:05 PMPPASS
There will be someone home. If you have any questions please feel free to contact Darren ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok cover S and N side of main level and small ceiling area at bottom of stairs.
ELE19-02897 Final8/4/20198/6/20198/6/2019 11:48:40 AMAPASS
Please call Bryce Waterman, Foreman with any questions:###-#### Phone #: ###-#### Inspection requested via web by Rob Maes Ok final. All labeling present,
ELE19-02019 Final8/5/20198/6/20198/6/2019 10:10:25 AMAPASS
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden Ok final.
ELE19-01095 Final8/5/20198/6/20198/6/2019 9:28:23 AMAFAIL
Ready for final inspection. Phone #: ###-#### Inspection requested via web by Michael Barrie
1. Lockout for hood.
2. Service recept for mini split system.
4. Weather proof covers for out switch and recepts.
5. Tamper resistant throughout.
6. Down size breaker for mini split. Needs to be 15a to match wire size from disconnect.
7. Weather proof cover for soffitt recept out back
ELE19-01404 Final8/5/20198/6/20198/6/2019 9:25:37 AMAPASS
It will be open. If you have any questions please feel free to contact Chaz ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Ok final
ELE17-02710 ELE-Aging Inspection8/6/20198/6/20198/6/2019 5:52:46 AM DONE
Please schedule a final inspection. Will need to bring 1 ea of equipt installed to verify UL listing. For future solar installations a RI inspection will be needed prior to install of any components.