Inspections for the day of: Thursday, August 7, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00440 INSP-Final Inspection8/6/20038/7/20038/7/2003 12:00:00 AMAFAIL
###-#### Hood suppression system operated correctly but needs to be connected to the existing fire alarm system. The electrical outlet underneath the hood did not turn off upon activation of the hood suppression system. Provide all documentation upon final 8/7/2003 9:02:14 AM
FIR03-00081 INSP-Sprinkler Rough-in8/6/20038/7/20038/7/2003 12:00:00 AMAFAIL
tate; Phone #: ###-#### Provide updated fire sprinkler drawings to the city with a floor plan that matches the actual wall layout and sprinkler piping layout. Pendant is missing a hanger in closet in east side of the building. In the same location piping is attached to wood supprt that is not completly attached to the trusses. All existing insulation needs to be removed from below the sprinkler piping. Provide access and ladder so all piping can be inspected. Provide tenting for sprinkler piping per approved plans and nfpa 13d with access for inspection 8/7/2003 3:21:54 PM
FIR03-00308 INSP-Final Inspection8/6/20038/7/20038/7/2003 12:00:00 AMAFAIL
Phone #: ###-#### The approved plans on site were missing the floor plan and the review notes. Duct detector did not shut down unit. 8/7/2003 9:33:07 AM
FIR03-00417 INSP-Sprinkler Rough-in/Hydro8/6/20038/7/20038/7/2003 12:00:00 AMPFAIL
could not get access the doors are locked 8/7/2003 2:59:15 PM
FIR03-00324 INSP-Final Inspection8/6/20038/7/20038/7/2003 12:00:00 AMPFAIL
Phone #: ###-#### Repair the nac circuit, change text to supervisory for the remote tamper switches, provide verify zones labels 8/7/2003 2:46:26 PM
BLD02-02629 FIRE-Final Inspection8/7/20038/7/20038/7/2003 12:00:00 AMPPASS
fire life safety finaled 8/8/2003 8:35:25 AM
FIR03-00418 INSP-Final Inspection8/7/20038/7/20038/7/2003 12:00:00 AMPFAIL
provide tag on the antifreeze system and hydro test the system 8/7/2003 2:43:40 PM