ELE07-02342
| Rough-In Permanent Service | 8/7/2007 | 8/7/2007 | 8/7/2007 3:14:57 PM | P | CANC |
|
|
Bob - WALLS ONLY. Thank You!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson needs seperate ele permits foe each T?I and shall be linked to correct BLD permit, and plans shall have reversed north south corrected
|
ELE07-02755
| Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 1:32:27 PM | P | PART |
|
|
this is for an underground insection, please call Jeremy Thornock with any questions Phone #: ###-#### Internet Inspection Request from: Sandee Johnson u/g from front bld to back bld ok
|
ELE07-02746
| Temporary Service | 8/7/2007 | 8/7/2007 | 8/7/2007 12:51:47 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas t/s u/g new ok
|
ELE07-02735
| Final | 8/6/2007 | 8/7/2007 | 8/7/2007 12:37:51 PM | A | CANC |
|
|
Tony Norton did the requested code corrections, please re-inspect Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer Inspection cancelled from web by: Jarrod Clymer
|
ELE07-02757
| Permanent Service | 8/7/2007 | 8/7/2007 | 8/7/2007 12:09:31 PM | P | CANC |
|
|
will start service change at 9:30 should take no longer than 3 hours.you can inspect around noon sometime.please let me know when idaho power can rehook up.thanks BILL ###-#### Phone #: ###-#### Internet Inspection Request from: Bob Glenn request should be for 08-08-07 called
|
ELE07-01322
| Final | 8/6/2007 | 8/7/2007 | 8/7/2007 10:38:33 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Gary Foreman ok
|
ELE07-01617
| Final | 8/7/2007 | 8/7/2007 | 8/7/2007 10:24:12 AM | P | PASS |
|
|
Thank You!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok card signed
|
ELE07-01940
| Rough-In Permanent Service | 8/6/2007 | 8/7/2007 | 8/7/2007 9:18:28 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/6/2007 at 12:51:11 PM. Contact: ###-####. p/s u/g new ok
|
ELE07-01722
| Electrical Rough-In | 8/6/2007 | 8/7/2007 | 8/7/2007 8:48:02 AM | A | PART |
|
|
ART GUERRERO - HE WILL BE @ THE JOB SITE Phone #: ###-#### Internet Inspection Request from: Randy Vail u/g ok
|
ELE07-02736
| Temporary Service | 8/6/2007 | 8/7/2007 | 8/6/2007 1:19:06 PM | A | FAIL |
|
|
###-#### Internet Inspection Request from: Todd Holbrook corr. called 312.5 needs conn for GEC, 250.24 GEC shall be terminated to neutral at t/s, 110.12(C) clean dirt from t/s and meter, 110.3(A) tighten all locknuts and screws
|