ELE07-02398
| Conference | 8/7/2007 | 8/7/2007 | 8/7/2007 5:42:51 PM | P | DONE |
|
|
matt ###-#### Phone #: ###-#### talked about number of inspections, seeing all wiring before cover, being available for inspection by requestor
|
ELE07-02662
| Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 2:54:41 PM | P | FAIL |
|
|
mike - swimming pool conduit Phone #: ###-#### called, left corr notice, left message, nec 300.5 raceways shall be 18" deep to top of conduit, 352.26 rnc shall not have over 360 degree total bends between pull points, BCC shall see all u/g before cover
|
ELE07-02286
| Permanent Service | 8/6/2007 | 8/7/2007 | 8/7/2007 2:09:56 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Steve p/s, exst meter pak, n, ok
|
ELE07-02285
| Permanent Service | 8/6/2007 | 8/7/2007 | 8/7/2007 1:34:39 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig p/s, exst meter pak, n, ok
|
ELE07-02752
| Rough-In Permanent Service | 8/7/2007 | 8/7/2007 | 8/7/2007 12:45:15 PM | P | NR |
|
|
DAVE - HE WILL MEET @ JOBSITE Phone #: ###-#### Internet Inspection Request from: Randy Vail cslled contr, no riser , no closure plate in top panel
|
ELE07-00974
| Final | 8/6/2007 | 8/7/2007 | 8/7/2007 10:31:28 AM | A | PASS |
|
|
dean Phone #: ###-#### called, left survey notice, nec 408.4 swhall provide clear and concise circuit directory, 334.30 nm cable shall be stapled within 12" of panel, 406.8 (B) recpt shall have weatherproof provisions whether or not plug inserted, ok to final
|
ELE07-02706
| Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 9:28:55 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Todd Holbrook called contr about ent protection, rest corrections made, ric hard lids and walls ok
|
ELE07-02342
| Rough-In Permanent Service | 8/7/2007 | 8/7/2007 | 8/7/2007 8:40:50 AM | A | CANC |
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|
ELE07-02579
| Electrical Rough-In | 8/6/2007 | 8/7/2007 | 8/7/2007 8:39:19 AM | A | PASS |
|
|
equal pot. & potting compound inspection on swimming pool Phone #: ###-#### Internet Inspection Request from: Jari Rivers potting and equi-pot plane ok to pour
|
ELE07-02547
| Electrical Rough-In | 8/7/2007 | 8/7/2007 | 8/7/2007 8:04:51 AM | A | PART |
|
|
Contact is Perry. U/G in Produce. Phone #: ###-#### Internet Inspection Request from: David Bonner main runs u/g in produce area ok to cover
|