Inspections for the day of: Tuesday, August 7, 2007.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01201 FIRE-Final Inspection8/7/20078/7/20078/8/2007 9:10:10 AMPPART
The new insulation backing has been installed in tenant spaces 10448, 10374 and 10366 and appears ok.
BLD07-00054 FIRE-Final Inspection8/7/20078/7/20078/7/2007 4:10:24 PMPPASS
life safety passed
FIR07-00497 INSP-Sprinkler Rough-in/Hydro8/6/20078/7/20078/7/2007 4:09:24 PMAPASS
Hydro tests for the anti-freeze system and the overhead system passed.
BLD07-00055 FIRE-Final Inspection8/6/20078/7/20078/7/2007 3:13:09 PMPPASS
life safety passed.
FIR07-00459 INSP-Sprinkler Rough-in8/7/20078/7/20078/7/2007 3:10:56 PMPPASS
The remaining underground supply piping is ok to cover.
FIR07-00530 INSP-Sprinkler Rough-in8/6/20078/7/20078/7/2007 1:51:13 PMAFAIL
The tenting isn't satifactory and one piece of piping as marked on the plans has been installed as 1" wereas the plans indicate 1 1/4" is to be installed. The riser is too far off of the wall as well and is not completely built yet.
BLD07-02047 FIRE-Final Inspection8/7/20078/7/20078/7/2007 1:43:38 PMPFAIL
Provide the building address near the entrance as discussed, remove the locking hardware from the exit door from the restroom into this tenant space, provide lever hardware on all of the office doors as discussed, provide passage hardware on the door to the north exit corridor, repair all exit signs and emergency lights.