FIR08-00136
| INSP-Final Inspection | 8/5/2008 | 8/7/2008 | 8/7/2008 4:35:26 PM | P | PASS |
|
|
Fire alarm testing passed, permit finaled.
|
FIR08-00214
| INSP-Final Inspection | 8/5/2008 | 8/7/2008 | 8/7/2008 4:31:58 PM | P | PASS |
|
|
OH fire sprinkler permit finaled, notified contractor to request project related UG supply permit for final.
|
FIR08-00535
| INSP-Final Inspection | 8/7/2008 | 8/7/2008 | 8/7/2008 4:27:41 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00928
| INSP-Sprinkler Rough-in/Hydro | 8/6/2008 | 8/7/2008 | 8/7/2008 4:26:12 PM | A | FAIL |
|
|
Overhead rough-in inspection for the 6th, 5th, 4th and 3rd floors failed due to items including hangers in need of adjustment, heads exceeding min. spacing guidelines, overspaced heads, "shadowing" at some areas, noted corridors not yet complete, both stair enclosures will require coverage due to combustible construction per NFPA 13 8.15.3.1. See plan set for annotations regarding corrections indicated. NOTE: Hydrostatic testing for the 6th and 4th floors passed.
|
FIR08-00535
| INSP-Conference | 8/5/2008 | 8/7/2008 | 8/7/2008 1:07:49 PM | A | DONE |
|
|
Fire alarm demo work per permit scope completed acceptable.
|
BLD07-02405
| FIRE-Conference | 8/6/2008 | 8/7/2008 | 8/7/2008 10:59:23 AM | A | DONE |
|
|
Remainder of building shell life safety issues are finished.
|
BLD08-01501
| FIRE-Final Inspection | 8/6/2008 | 8/7/2008 | 8/7/2008 10:55:48 AM | A | PASS |
|
|
Items on correction notice have been completed, fire life safety passed.
|
BLD08-01215
| FIRE-Final Inspection | 8/7/2008 | 8/7/2008 | 8/7/2008 10:34:03 AM | A | PASS |
|
|
Life safety inspection passed, contractor to relocate building address numbers to comply with requirements for a contrasting backround visible from the street per IFC 2006 sec. 505.1.
|
FIR08-00512
| INSP-Final Inspection | 8/7/2008 | 8/7/2008 | 8/7/2008 10:21:09 AM | P | CANC |
|
|
warner Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|