FIR17-00305
| INSP-Sprinkler Rough-in | 8/4/2017 | 8/7/2017 | 8/7/2017 3:24:31 PM | A | PART |
|
|
Rough to cover for 7'-0" from the building only. The remaining piping was not installed by Shilo. A separate permit will be required for this work from a licensed sprinkler contractor or Shilo will need to accept responcibility for this work. Shilo will need to resubmit plans for a change of scope. Plans need to be submitted showing the additional fittings in the underground supply line. Per Brian, the installer, the top of pipe is 5'-1" at the doorway/floor and is at 4'-9" at the connection. There is no sidewalk or land scaping just smooth travel from the door to the low point in the parking lot. If changes are made in the parking lot piping will need to be dug up and modified to the correct depth.
|
FIR17-00198
| INSP-Sprinkler Rough-in/Hydro | 8/7/2017 | 8/7/2017 | 8/7/2017 1:51:25 PM | P | PASS |
|
|
Underground hydro test passed
|
FIR17-00405
| INSP-Sprinkler Rough-in | 8/4/2017 | 8/7/2017 | 8/7/2017 11:49:37 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR17-00278
| INSP-Sprinkler Rough-in | 8/4/2017 | 8/7/2017 | 8/7/2017 11:47:15 AM | A | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR17-00359
| INSP-Final Inspection | 8/4/2017 | 8/7/2017 | 8/7/2017 10:33:40 AM | A | PASS |
|
|
Permit finaled
|
NAF17-00053
| INSP-Final | 8/4/2017 | 8/7/2017 | 8/7/2017 12:00:00 AM | A | PASS |
|
|
Phone #: 2088698456 >> Inspection requested via mobile web by Wes Flacker-
|