Inspections for the day of: Tuesday, August 7, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00591 INSP-Sprinkler Rough-in8/6/20188/7/20188/7/2018 2:06:59 PMPPART
Rough to cover inspection for overhead fire sprinkler piping located above the hardlids and the east section of the tenant space complete, hardlids and east section of TI approved for cover. West side of TI will be inspected at a later date.

Rick Clark is the contact for this partial rough to cover inspection. We appreciate your help. thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
FIR18-00486 INSP-Sprinkler Rough-in8/7/20188/7/20188/7/2018 2:05:49 PMPPART
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping located between conditioned spaces approved for cover, piping located in unconditioned spaces cannot be covered until a tenting inspection is performed.
FIR18-00486 INSP-Sprinkler Rough-in/Hydro8/6/20188/7/20188/7/2018 2:03:13 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Call Anthony to coordinate Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR17-00694 INSP-Final Inspection8/3/20188/7/20188/7/2018 10:47:02 AMACANC
Fire alarms are not ready per conversation with point of contact, inspection request will be rescheduled to coincide with fire alarm inspection, this request is cancelled.

Phone #: ###-#### Inspection requested via web by Stan Beus
BLD18-01802 FIRE-Final Inspection8/6/20188/7/20188/7/2018 10:07:46 AMAPASS
Final life fire safety inspection complete.

Doug Phone #: ###-####
BLD17-01238 FIRE-Final Inspection8/6/20188/7/20188/7/2018 9:41:17 AMAPASS
Final life fire safety inspection for area of work complete.

Dale Phone #: ###-####
FIR18-00403 INSP-Final Inspection8/6/20188/7/20188/7/2018 9:14:33 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00404 INSP-Final Inspection8/6/20188/7/20188/7/2018 9:14:15 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00378 INSP-Final Inspection8/6/20188/7/20188/7/2018 9:13:35 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
BLD18-01688 FIRE-Conference8/7/20188/7/20188/7/2018 8:12:33 AMADONE
During the rough-in inspection for newly installed overhead fire sprinkler piping it was noticed that the premise still has o-ring style heads throughout the building that need to be replaced (O-ring style heads must be replaced due to o-ring style sprinkler heads failing to operate correctly). O-ring style heads must be replaced before fire sprinkler final inspection and fire life safety inspection. After discussion with Ron Johnson with Boise Fire, final inspections will be failed on fire sprinkler and life safety if o-ring style heads are not replaced.
FIR18-00582 INSP-Conference8/7/20188/7/20188/7/2018 8:11:53 AMADONE
During the rough-in inspection for newly installed overhead fire sprinkler piping it was noticed that the premise still has o-ring style heads throughout the building that need to be replaced (O-ring style heads must be replaced due to o-ring style sprinkler heads failing to operate correctly). O-ring style heads must be replaced before fire sprinkler final inspection and fire life safety inspection. After discussion with Ron Johnson with Boise Fire, final inspections will be failed on fire sprinkler and life safety if o-ring style heads are not replaced.
FIR18-00582 INSP-Sprinkler Rough-in8/6/20188/7/20188/7/2018 8:03:28 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

Todd Phone #: ###-####