Inspections for the day of: Tuesday, August 8, 1995.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC95-00357 INSP - Gas pressure test8/8/19958/8/19958/8/1995 12:00:00 AM PASS
#27992
MEC95-00357 INSP - Framing/ Rough-in8/8/19958/8/19958/8/1995 12:00:00 AM PASS
25 MIN
MEC95-00357 INSP - Framing/ Rough-in8/8/19958/8/19958/8/1995 12:00:00 AM PART
PARTIAL STILL NEEDS R/A PIPE 20 MIN
MEC95-00414 INSP - Framing/ Rough-in8/8/19958/8/19958/8/1995 12:00:00 AM PASS
15 MIN
MEC95-00432 INSP - Final8/8/19958/8/19958/8/1995 12:00:00 AM PASS
CORRECTIONS MADE FINAL SIGNED CARD 20 MIN
MEC95-00436 INSP - Final8/8/19958/8/19958/8/1995 12:00:00 AM
27988 GAS OK RTU OK 25 MIN
MEC95-00442 INSP - Gas pressure test8/8/19958/8/19958/8/1995 12:00:00 AM PASS
#27997 ATTIC FURN. OK NEED WRAP 2 ELLS
MEC95-00445 INSP - Gas pressure test8/8/19958/8/19958/8/1995 12:00:00 AM PASS
#27991
MEC95-00445 INSP - Framing/ Rough-in8/8/19958/8/19958/8/1995 12:00:00 AM PASS
20 MIN
MEC3047662 INSP - Final8/8/19958/8/19958/8/1995 12:00:00 AM PASS
35 MIN
MEC95-00018 INSP - Final8/8/19958/8/19958/8/1995 12:00:00 AMAPASS
final ok 20 min
MEC95-00038 INSP - Final8/8/19958/8/19958/8/1995 12:00:00 AMAFAIL
need: condensate drain fastened down, gas cock outside of furnace, rangehood to exhaust outdoors. 25 min
MEC95-00416 INSP - Gas pressure test8/8/19958/8/19958/8/1995 12:00:00 AMAPASS
gas piping ok #27990 15 min
PLM95-00415 INSP - Framing/ Rough-in8/8/19958/8/19958/8/1995 12:00:00 AMPPASS
08/08/95 350 - DCT -OK DIFFUSERS/DUCTWORK GP -OK GAS PIPING#37568