Inspections for the day of: Tuesday, August 8, 2000.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00072 INSP-Sprinkler Rough-in/Hydro8/7/20008/8/20008/8/2000 12:00:00 AMAPART
hydro on the underground and a flush ###-#### don pager hydro okay on underground 8/8/2000 11:22:53 AM
FIR00-00072 INSP-Supply line flush8/8/20008/8/20008/8/2000 12:00:00 AMANR
not ready to test FDC 8/8/2000 11:23:22 AM
BLD99-03348 FIRE-Alarm Testing8/8/20008/8/20008/8/2000 12:00:00 AMPFAIL
Jim ###-#### tested the alarms: batteries need to be 55 amp; trouble on NACs activate the alarms; complete the wiring/horns in attice; F/S dampers not tested - not accessible; need exit sign; 2 hr and 1 hr wall penetrations 8/9/2000 8:40:30 AM
BLD00-01306 FIRE-Final Inspection8/8/20008/8/20008/8/2000 12:00:00 AMPPASS
DAVID-- ###-#### FIRE FN
FIR00-00072 INSP-Supply line flush8/8/20008/8/20008/8/2000 12:00:00 AMPPASS
Scheduled by Inspector: 409 On 8/8/2000 undergound flush of FDC and supply line okay 8/9/2000 8:28:36 AM