FIR02-00277 INSP-Sprinkler Rough-in/Hydro8/7/20028/8/20028/8/2002 12:00:00 AMAFAIL
sprinkler head in entry is overspaced 8/8/2002 11:25:36 AM
BLD02-00500 FIRE-Final Inspection8/7/20028/8/20028/8/2002 12:00:00 AMAPASS
fire life/safety finaled 8/8/2002 2:51:07 PM
BLD02-00137 FIRE-Final Inspection8/7/20028/8/20028/8/2002 12:00:00 AMAFAIL
provide tamper switches on the valves for the fire pump and the fire sprinkler riser.These switches are to be monitored by the fire alarm system. The bypass valve for the fire pump is in the open position. Provide information as to why and close the valve. Provide supervision of the new duct smoke detector by the fire alarm panel. Provide approved fire alarm drawings for items 1 and 4 on the correction notice. Sprinkler heads in the phone room and the radio room are overspaced. Verify beam blockage in radio room 8/8/2002 11:24:16 AM
BLD02-00567 FIRE-Supply Line Flush8/8/20028/8/20028/8/2002 12:00:00 AMPPASS
This inspection done under FIR02-00061 8/8/2002 3:41:47 PM
FIR02-00061 INSP-Supply line flush8/8/20028/8/20028/8/2002 12:00:00 AMPPASS
flush OK