Inspections for the day of: Friday, August 8, 2003.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00019 INSP-Final Inspection8/7/20038/8/20038/8/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 8/7/2003 at 1:58:31 PM. Contact: ###-####.
BLD03-01335 FIRE-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMAFAIL
Provide fire extinguisher per review note #5, Verify HVAC system requirements per note #32, Provide approved door hardware on both store front doors or remove the second door per plans, Provide access to panel for fire alarm system per note #13
FIR03-00312 INSP-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPPASS
fire sprinklers finaled
FIR03-00328 INSP-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPPASS
fire sprinklers finaled
BLD03-01351 FIRE-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPFAIL
Fire alarm permit needs to be finaled. Life safety items are OK
BLD03-01428 FIRE-Final Inspection8/7/20038/8/20038/8/2003 12:00:00 AMPPASS
fire life safety finaled 8/8/2003 9:49:13 AM 8/8/2003 9:49:47 AM
BLD99-01399 FIRE-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPPASS
###-#### Fire life safety is Ok 8/8/2003 2:11:41 PM
BLD03-01000 FIRE-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPFAIL
###-#### Need fire alarm permit that is attached to the library /computer lab building permit finaled. Fire life safety is ok 8/8/2003 2:11:19 PM
FIR03-00419 INSP-Supply line flush8/8/20038/8/20038/8/2003 12:00:00 AMPFAIL
Inspection was for bury on the underground supply line. The last section of pipe and the pipe into the building does not have the minimum 4'-6" bury and will need to be lower 8/8/2003 3:57:44 PM
FIR03-00417 INSP-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPPASS
We will not be present. Call if you need us there. Inspection reports on site. Tag to follow from property owner.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
FIR03-00417 INSP-Final Inspection8/8/20038/8/20038/8/2003 12:00:00 AMPPASS
We will not be present. Call if you need us there. Inspection reports on site. Tag to follow from property owner.; Phone #: ###-#### Internet Inspection Request from: Trent Bice