FIR05-00385
| INSP-Supply line flush | 8/8/2005 | 8/8/2005 | 8/8/2005 4:43:41 PM | P | CANC |
|
|
Cancel inspection per Sam, not ready, will reschedule for tomorrow.
|
FIR05-00315
| INSP-Sprinkler Rough-in/Hydro | 8/8/2005 | 8/8/2005 | 8/8/2005 4:42:19 PM | P | PART |
|
|
UG fire supply hydrostatic test passed.
|
FIR04-00350
| INSP-Final Inspection | 8/8/2005 | 8/8/2005 | 8/8/2005 2:53:09 PM | P | PASS |
|
|
Fire sprinkler permit is finaled.
|
FIR03-00737
| INSP-Final Inspection | 8/5/2005 | 8/8/2005 | 8/8/2005 2:52:08 PM | P | FAIL |
|
|
Provide stamped approved plans on site for inspection, HVAC units need to be operable for duct smoke detection testing, PIV tamper is not programed correctly, provide lock and label at breaker in panel for FACP, clear trouble at knox box, test remaining alarm devices.
|
FIR05-00385
| INSP-Sprinkler Rough-in/Hydro | 8/8/2005 | 8/8/2005 | 8/8/2005 1:05:26 PM | P | CANC |
|
|
Cancel inspection per Sam with Treasure Valley Sprinkler.
|
BLD05-02008
| FIRE-Final Inspection | 8/8/2005 | 8/8/2005 | 8/8/2005 11:39:54 AM | P | FAIL |
|
|
Provide approved hardware at man door in relocated wall, verify provision of a fire extinguisher with current inspection tag.
|
BLD05-01273
| FIRE-Final Inspection | 8/8/2005 | 8/8/2005 | 8/8/2005 10:58:09 AM | P | PASS |
|
|
Fire life safety passed inspection, suite number has changed per owner to 110 as posted at tenant main doors.
|
BLD04-01353
| FIRE-Final Inspection | 8/5/2005 | 8/8/2005 | 8/8/2005 10:18:34 AM | A | PASS |
|
|
Items on correction notice from 10/22/04 have been corrected. Life safety finaled.
|
FIR05-00304
| INSP-Final Inspection | 8/8/2005 | 8/8/2005 | 8/8/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-02008
| FIRE-Final Inspection | 8/8/2005 | 8/8/2005 | 8/8/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety passed inspection.
|