Inspections for the day of: Monday, August 8, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02769 FIRE-Final Inspection8/8/20058/8/20058/8/2005 4:20:35 PMPPASS
Life safety finaled
FIR05-00255 INSP-Final Inspection8/1/20058/8/20058/8/2005 4:16:56 PMPFAIL
As per sam rogers, two additional duct smoke detectors are required
FIR04-00257 INSP-Conference8/8/20058/8/20058/8/2005 3:45:06 PMPDONE
Review new fryer dimensions. It appears that it will provide the required 6" clearance when installed. The BBQ at the other end of the hood will be relocated under the hood. These items to be verified when new fryer is installed.
MIS05-00110 FIR-Final8/5/20058/8/20058/8/2005 3:43:19 PMPFAIL
See city approved plans for locations of additional exit signs and emergency lights and door hardware corrections. Owner needs to take plans back to plan review for approval and changing scope of work to show exiting through the separate tenant. This is due to an overhead door that is used to block the only direct to the exterior exit for the warehouse area. Per Bill Alexander it appears the storage in this building is class 4 and with the information provided by me the sprinkler system is adequate for storage to 10'.
FIR05-00430 INSP-Final Inspection8/8/20058/8/20058/8/2005 2:06:21 PMPPASS
Fire sprinkler permit finaled
FIR05-00346 INSP-Sprinkler Rough-in/Hydro8/8/20058/8/20058/8/2005 1:30:29 PMPPASS
Additional branchline and hydro test passed. Tom needs to provide test papers at next inspection
FIR04-00531 INSP-Final Inspection8/5/20058/8/20058/8/2005 12:39:37 PMAPASS
Fire sprinkler permit finaled
BLD04-02128 FIRE-Final Inspection8/5/20058/8/20058/8/2005 10:40:36 AMAFAIL
Contact: ###-####.
Provide sticker at the main exit per note #25. Provide indicator for the lock at the main exit. Remove thumbturn and provide approved hardware on the west exterior door. Provide exit discharge lighting per review note #18
MIS05-00116 FIR-Final8/5/20058/8/20058/8/2005 10:06:09 AMAPART
josh bode; Phone #: ###-#### A temporary occupancy was given until the fire extinguisher is mounted and tagged and the sticker is provided at the main exit.