Inspections for the day of: Tuesday, August 8, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01427 ELE-Aging Inspection8/8/20068/8/20068/10/2006 10:15:04 AM DONE
called, elect said waiting for field evaluation on generator.
ELE06-02880 Electrical Rough-In8/7/20068/8/20068/8/2006 4:13:19 PMPPASS
POTTING & BONDING INSPECTION FOR SWIMMING POOL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall potting and bonding ok, equipotential plane ok to pour
ELE06-02890 Rough-In Permanent Service8/8/20068/8/20068/8/2006 3:19:52 PMPPASS
Scheduled by a contractor via Hello! on 8/8/2006 at 9:42:59 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
ELE06-02355 Permanent Service8/8/20068/8/20068/8/2006 2:19:16 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange p/s, exst u/g, n, ok
ELE06-00815 ELE-Aging Inspection8/8/20068/8/20068/8/2006 2:16:59 PM DONE
see final
ELE06-00815 Final8/8/20068/8/20068/8/2006 2:16:25 PMPPASS
looked at sign, ok to final
ELE06-01085 ELE-Aging Inspection8/8/20068/8/20068/8/2006 2:03:04 PM NR
suc
ELE06-01583 Final8/8/20068/8/20068/8/2006 1:59:31 PMPPASS
james; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ok to final
ELE06-02906 Electrical Rough-In8/8/20068/8/20068/8/2006 1:31:30 PMPPASS
craig - buried cable; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g only house to garage
ELE06-02788 Electrical Rough-In8/8/20068/8/20068/8/2006 1:05:30 PMPPASS
checked jetted tub, label ok, need to check access at final
ELE06-02800 Electrical Rough-In8/7/20068/8/20068/8/2006 11:53:06 AMAPART
Scheduled by a contractor via Hello! on 8/7/2006 at 3:10:43 PM. Contact: ###-####. u/g for elect room ok to cover
ELE06-02798 Final8/7/20068/8/20068/8/2006 10:12:57 AMAFAIL
adam ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called, left corr notice, nec 230.24(B)(4) minimum clearance from ground shall be 18' on other than residential property, 312.5 all conductors entering enclosures shall have abrasion protection, 230.28 mast shall be supported by guy kit, 250.53(G) ground rods shall be flush with or below ground level
ELE06-02914 Electrical Rough-In8/7/20068/8/20068/8/2006 9:51:52 AMAPASS
brandon ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
ELE06-02926 Permanent Service8/7/20068/8/20068/8/2006 8:53:06 AMAFAIL
jean - #5 ID Power reconnect insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 112.12(C) there shall be no broken parts, BCC verify address and space#
ELE06-02613 Rough-In Permanent Service8/7/20068/8/20068/8/2006 8:25:50 AMAPASS
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford stub wall 1st floor ric ok, p/s exst meter pak, n ok, 2 meters