ELE06-01427
| ELE-Aging Inspection | 8/8/2006 | 8/8/2006 | 8/10/2006 10:15:04 AM | | DONE |
|
|
called, elect said waiting for field evaluation on generator.
|
ELE06-02880
| Electrical Rough-In | 8/7/2006 | 8/8/2006 | 8/8/2006 4:13:19 PM | P | PASS |
|
|
POTTING & BONDING INSPECTION FOR SWIMMING POOL. THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall potting and bonding ok, equipotential plane ok to pour
|
ELE06-02890
| Rough-In Permanent Service | 8/8/2006 | 8/8/2006 | 8/8/2006 3:19:52 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/8/2006 at 9:42:59 AM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
ELE06-02355
| Permanent Service | 8/8/2006 | 8/8/2006 | 8/8/2006 2:19:16 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange p/s, exst u/g, n, ok
|
ELE06-00815
| ELE-Aging Inspection | 8/8/2006 | 8/8/2006 | 8/8/2006 2:16:59 PM | | DONE |
|
|
see final
|
ELE06-00815
| Final | 8/8/2006 | 8/8/2006 | 8/8/2006 2:16:25 PM | P | PASS |
|
|
looked at sign, ok to final
|
ELE06-01085
| ELE-Aging Inspection | 8/8/2006 | 8/8/2006 | 8/8/2006 2:03:04 PM | | NR |
|
|
suc
|
ELE06-01583
| Final | 8/8/2006 | 8/8/2006 | 8/8/2006 1:59:31 PM | P | PASS |
|
|
james; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ok to final
|
ELE06-02906
| Electrical Rough-In | 8/8/2006 | 8/8/2006 | 8/8/2006 1:31:30 PM | P | PASS |
|
|
craig - buried cable; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g only house to garage
|
ELE06-02788
| Electrical Rough-In | 8/8/2006 | 8/8/2006 | 8/8/2006 1:05:30 PM | P | PASS |
|
|
checked jetted tub, label ok, need to check access at final
|
ELE06-02800
| Electrical Rough-In | 8/7/2006 | 8/8/2006 | 8/8/2006 11:53:06 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 8/7/2006 at 3:10:43 PM. Contact: ###-####. u/g for elect room ok to cover
|
ELE06-02798
| Final | 8/7/2006 | 8/8/2006 | 8/8/2006 10:12:57 AM | A | FAIL |
|
|
adam ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called, left corr notice, nec 230.24(B)(4) minimum clearance from ground shall be 18' on other than residential property, 312.5 all conductors entering enclosures shall have abrasion protection, 230.28 mast shall be supported by guy kit, 250.53(G) ground rods shall be flush with or below ground level
|
ELE06-02914
| Electrical Rough-In | 8/7/2006 | 8/8/2006 | 8/8/2006 9:51:52 AM | A | PASS |
|
|
brandon ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok
|
ELE06-02926
| Permanent Service | 8/7/2006 | 8/8/2006 | 8/8/2006 8:53:06 AM | A | FAIL |
|
|
jean - #5 ID Power reconnect insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 112.12(C) there shall be no broken parts, BCC verify address and space#
|
ELE06-02613
| Rough-In Permanent Service | 8/7/2006 | 8/8/2006 | 8/8/2006 8:25:50 AM | A | PASS |
|
|
any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford stub wall 1st floor ric ok, p/s exst meter pak, n ok, 2 meters
|