Inspections for the day of: Friday, August 8, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00830 INSP-Final Inspection8/7/20088/8/20088/11/2008 10:09:34 AMADEFR
Inspection scheduled 8/11 per discussion.
FIR08-00130 INSP-Final Inspection8/7/20088/8/20088/8/2008 4:28:14 PMPDEFR
Rescheduled for Monday, 8/11.
BLD07-00007 FIRE-Final Inspection8/7/20088/8/20088/8/2008 4:27:03 PMPNR
Project is not in condition for final life safety at this time due to construction/finish work in progress, area A is not complete, both elevators are not functional, kitchen hood is not ready for final inspection and testing, site work still underway, noted temporary address and max occupant load signs, tested exit signs and EM lights for areas B, C, and D first floor-noted five exit signs in need of repair. Hydrants, fire extinguishers, and door hardware appear acceptable for areas inspected to date. Discussed project schedule.
FIR08-00255 INSP-Final Inspection8/6/20088/8/20088/8/2008 4:21:29 PMAPART
Refer to red-lines on approved plan set for noted deficiencies and remainder of work to be completed and inspected.
FIR08-00477 INSP-Final Inspection8/7/20088/8/20088/8/2008 12:38:05 PMAPASS
Fire alarm testing passed inspection, permit finaled.
FIR08-00452 INSP-Sprinkler Rough-in8/7/20088/8/20088/8/2008 11:54:30 AMAPART
2nd floor overhead work at the classrooms is approved for cover, noted modifications at the corridor to be indicated on as-built plans per discussion with the designer, basement area is missing five escutcheons at pendent heads.
FIR08-00503 INSP-Sprinkler Rough-in8/7/20088/8/20088/8/2008 11:50:48 AMAPART
Items on correction notice are finished, overhead fire sprinkler system modifications are okay for cover at the drop ceilings.
BLD08-00921 FIRE-Final Inspection8/7/20088/8/20088/8/2008 11:00:08 AMAPASS
Corrections verified for compliance, shell permit finaled, duct detectors deleted due to cfm below 2000, life safety inspection passed.
BLD08-00668 FIRE-Final Inspection8/7/20088/8/20088/8/2008 10:30:30 AMAPASS
Fire life safety inspection passed.