ELE12-00850
| ELE-Aging Inspection | 8/8/2014 | 8/8/2014 | 8/8/2014 1:45:44 PM | | DONE |
|
|
Waiting for contractor to schedule
|
ELE14-02046
| Electrical Rough-In | 8/7/2014 | 8/8/2014 | 8/8/2014 1:42:55 PM | P | PASS |
|
|
need approval to cover walls. Phone #: ###-#### Inspection requested via web by Alan Lusk When job started with service change listed this address with unit A and B. Wall rough in unit B or 2774. Wall rough in ok cover
|
ELE14-02182
| Temporary Service | 8/8/2014 | 8/8/2014 | 8/8/2014 1:15:23 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-02017
| Permanent Service | 8/7/2014 | 8/8/2014 | 8/8/2014 12:37:53 PM | A | PASS |
|
|
Contact - Tod Phone #: ###-#### Inspection requested via web by Harvey Reyna p/s o/h rec ok
|
ELE14-02183
| Permanent Service | 8/8/2014 | 8/8/2014 | 8/8/2014 12:04:34 PM | P | PASS |
|
|
Barry ###-#### p/s o/h n ok
|
ELE14-01963
| Temporary Service | 8/7/2014 | 8/8/2014 | 8/8/2014 11:18:48 AM | A | PASS |
|
|
Temporary power pole next to McAlvain''s trailer. Phone #: ###-#### Inspection requested via web by Rafael Castillo Informed contractor of 6x6" minimum required by Idaho Power. 4x6" present short swing. t/s o/h n ok
|
ELE14-01963
| Electrical Rough-In | 8/7/2014 | 8/8/2014 | 8/8/2014 11:14:52 AM | A | PASS |
|
|
Rough in of boxes and conduit in shear wall in southwest part of building. Phone #: ###-#### Inspection requested via web by Rafael Castillo Under ground and mason boxes marked on contracor print rough in ok cover
|
ELE14-01978
| Rough-In Permanent Service | 8/7/2014 | 8/8/2014 | 8/8/2014 10:18:14 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears 250.53(D)(2)- When rod is used for grounding electrode system for permenant service supplemental rod required. 330.30- MC cable shall be supported at inervals not exceeding 6'
|
ELE14-01979
| Rough-In Permanent Service | 8/7/2014 | 8/8/2014 | 8/8/2014 10:16:16 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears 250.53(D)(2)- When rod is used as grounding electrode system for permenant service supplemental rod required. 330.30- MC cable shall be supported at intervals not exceeding 6'
|
ELE14-02181
| Final | 8/8/2014 | 8/8/2014 | 8/8/2014 9:25:13 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kotton Corder Final ok
|
ELE14-02181
| Permanent Service | 8/8/2014 | 8/8/2014 | 8/8/2014 9:24:21 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kotton Corder Replaced broken hub. p/s o/h rec ok
|
ELE14-01701
| Final | 8/7/2014 | 8/8/2014 | 8/8/2014 9:14:59 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov All units kitchen bar devices shall have covers. Fire alarm wire shall have box.
|
MIS14-00162
| ELE-Conference | 7/25/2014 | 8/8/2014 | 7/25/2014 10:13:37 AM | A | CANC |
|
|
Reinspect unit for corrections compiance
|