Inspections for the day of: Monday, August 8, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00757 FIR-Aging Inspection8/8/20168/8/20168/15/2016 12:37:43 PM NR
Contractor is out of business
FIR16-00373 INSP-Sprinkler Rough-in/Hydro8/8/20168/8/20168/8/2016 2:59:04 PMPPASS
Rough-in passed. Piping can be covered.
FIR16-00490 INSP-Final Inspection8/5/20168/8/20168/8/2016 2:52:40 PMPPASS
Permit finaled
BLD15-00516 FIRE-Final Inspection8/5/20168/8/20168/8/2016 2:50:23 PMAFAIL
Need to finish life safety. Today I verified smoke alarms, fire dept access, fire hydrants, need for new address numbers, ships ladder to roof. I let the contractor know that the separate permit for the swimming pool needs to be finaled prior to the main building being signed off. To finish out I need to have the project related fire alarm and fire sprinkler permits finaled, fire extinguishers verifed, exit signs and emergency light verified, door hardware, roof access signage, riser room signage, fire dept access signage.
FIR15-00836 INSP-Final Inspection8/8/20168/8/20168/8/2016 1:50:01 PMPFAIL
We did not perform any actual testing today. I noted that the forward flush vavle was wired wrong, missing ceiling mounted horn/strobe, wrong batteries in the facp and four Bedrooms with the smoke detectors mounted less than 3'-0" from ceiling fans, PIV took 4 turns to activate tamper switch and the flow switch timing has not been verified.
BLD16-02711 FIRE-Final Inspection8/8/20168/8/20168/8/2016 12:16:12 PMPFAIL
Project is not ready for a final inspection yet. I noted that the new walls appear to be spaced adequately from the existing upright sprinkler protection.
FIR15-00709 INSP-Final Inspection8/8/20168/8/20168/8/2016 11:36:03 AMPFAIL
Need outside alarm bell installed and tested, need flow switches tested, need as-builts, need damaged heads replaced and missing canopies and ceiling tile installed. Need revised floor plan/wall layout for laundry area.
FIR16-00087 INSP-Alarm Testing8/5/20168/8/20168/8/2016 11:32:46 AMADONE
Need data sheets, breaker locks and locations, test flow switches, test outside alarm bell, document box, map at the facp, test elevator recall
BLD16-02419 FIRE-Final Inspection8/8/20168/8/20168/8/2016 10:39:30 AMPPASS
life safety passed