FIR07-00757
| FIR-Aging Inspection | 8/8/2016 | 8/8/2016 | 8/15/2016 12:37:43 PM | | NR |
|
|
Contractor is out of business
|
FIR16-00373
| INSP-Sprinkler Rough-in/Hydro | 8/8/2016 | 8/8/2016 | 8/8/2016 2:59:04 PM | P | PASS |
|
|
Rough-in passed. Piping can be covered.
|
FIR16-00490
| INSP-Final Inspection | 8/5/2016 | 8/8/2016 | 8/8/2016 2:52:40 PM | P | PASS |
|
|
Permit finaled
|
BLD15-00516
| FIRE-Final Inspection | 8/5/2016 | 8/8/2016 | 8/8/2016 2:50:23 PM | A | FAIL |
|
|
Need to finish life safety. Today I verified smoke alarms, fire dept access, fire hydrants, need for new address numbers, ships ladder to roof. I let the contractor know that the separate permit for the swimming pool needs to be finaled prior to the main building being signed off. To finish out I need to have the project related fire alarm and fire sprinkler permits finaled, fire extinguishers verifed, exit signs and emergency light verified, door hardware, roof access signage, riser room signage, fire dept access signage.
|
FIR15-00836
| INSP-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 1:50:01 PM | P | FAIL |
|
|
We did not perform any actual testing today. I noted that the forward flush vavle was wired wrong, missing ceiling mounted horn/strobe, wrong batteries in the facp and four Bedrooms with the smoke detectors mounted less than 3'-0" from ceiling fans, PIV took 4 turns to activate tamper switch and the flow switch timing has not been verified.
|
BLD16-02711
| FIRE-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 12:16:12 PM | P | FAIL |
|
|
Project is not ready for a final inspection yet. I noted that the new walls appear to be spaced adequately from the existing upright sprinkler protection.
|
FIR15-00709
| INSP-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 11:36:03 AM | P | FAIL |
|
|
Need outside alarm bell installed and tested, need flow switches tested, need as-builts, need damaged heads replaced and missing canopies and ceiling tile installed. Need revised floor plan/wall layout for laundry area.
|
FIR16-00087
| INSP-Alarm Testing | 8/5/2016 | 8/8/2016 | 8/8/2016 11:32:46 AM | A | DONE |
|
|
Need data sheets, breaker locks and locations, test flow switches, test outside alarm bell, document box, map at the facp, test elevator recall
|
BLD16-02419
| FIRE-Final Inspection | 8/8/2016 | 8/8/2016 | 8/8/2016 10:39:30 AM | P | PASS |
|
|
life safety passed
|