Inspections for the day of: Thursday, August 9, 2001.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00143 FIR-Aging Inspection8/9/20018/9/20018/9/2001 12:00:00 AM NR
work in progress 8/9/2001 3:26:20 PM
FIR01-00298 FIR-Aging Inspection8/9/20018/9/20018/9/2001 12:00:00 AM NR
work hasn't started 8/15/2001 11:24:23 AM
BLD01-01082 FIRE-Final Inspection8/7/20018/9/20018/9/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 08/07/2001 at 16:39:51. Contact: . no electrical power - couldn't verify battery backup for emergency lights and exit signs. alarms tested and passed 8/9/2001 9:35:40 AM
BLD00-02752 FIRE-Final Inspection8/8/20018/9/20018/9/2001 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 08/08/2001 at 13:06:12. Contact: ###-####. items from previous correction notice weren't completed; fire sprinkler preaction system air pressure switch activated the "general fire alarm". alarm system not tested properly. reinspection fee added with parcel hold by Marsha per my request 8/9/2001 9:34:03 AM
BLD01-01449 FIRE-Final Inspection8/8/20018/9/20018/9/2001 12:00:00 AMAPASS
Josh ###-####
FIR01-00306 INSP-Final Inspection8/9/20018/9/20018/9/2001 12:00:00 AMAPASS
Scheduled by Inspector: 409 On 8/9/2001 7:57:13 AM
BLD01-01996 FIRE-Final Inspection8/9/20018/9/20018/9/2001 12:00:00 AMAPASS
Added by Inspector: 409 On 8/9/2001 10:18:36 AM
FIR98-00258 INSP-Final Inspection8/9/20018/9/20018/9/2001 12:00:00 AMPPASS
Added by Inspector: 409 On 8/9/2001 2:49:08 PM area fully sprinklered with preaction system; okay to remove FM 200 system.
BLD01-01696 FIRE-Sprinkler Rough-in8/9/20018/9/20018/9/2001 12:00:00 AMPFAIL
Added by Inspector: 409 On 8/9/2001 3:23:12 PM couldn't gain entry
BLD00-03594 FIRE-Final Inspection8/9/20018/9/20018/9/2001 12:00:00 AMPPASS
fire insp dan ###-####