Inspections for the day of: Monday, August 9, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00377 INSP-Final Inspection8/6/20048/9/20048/9/2004 12:00:00 AMACANC
PAT; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD04-00783 FIRE-Final Inspection8/6/20048/9/20048/9/2004 12:00:00 AMAFAIL
Emergency lights in each of the restrooms did not work. Upon closer inspection I found the battery leads corroded off of the backup batteries. Repair and test all emergency lights in school. 8/9/2004 10:05:28 AM
BLD04-01082 FIRE-Final Inspection8/6/20048/9/20048/9/2004 12:00:00 AMACANC
Contractor was not ready for inspection. I did notify him of two deficiancies I noticed. One being the smoke detector at the main entrance is overspaced. A second detector will be required and the second item is the smoke detector in the storage room needs to be mounted at the deck. 8/9/2004 3:38:15 PM
BLD04-01194 BLD-Conference8/9/20048/9/20048/9/2004 12:00:00 AMPDONE
I spoke to the contractor about door hardware requirements. Lever type is ok. Exit signs and emergency lights are not required but he was going to install them anyway. 8/9/2004 3:39:52 PM
BLD03-02403 BLD-Other8/9/20048/9/20048/9/2004 12:00:00 AMPDONE
I issued a citation to Romar Electric/Kurtis Carlson for violation of IFC 902.1 as adopted by Boise City Municipal Code section 7-01-02 for beginning installation of the fire alarm system without approved plans.
FIR04-00238 INSP-Conference8/9/20048/9/20048/9/2004 12:00:00 AMPDONE
I issued a citation to Romar Electric/Kurtis Carlson for violation of IFC 902.1 as adopted by Boise City Municipal Code section 7-01-02 for beginning installation of the fire alarm system without approved plans.