Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02778 Electrical Rough-In8/8/20078/9/20078/9/2007 4:14:46 PMPPASS
NEED THE UNDERGROUND CONDUITS INSPECTED PRIOR TO THE CONCRETE SLAB BEING POURED. THANK YOU Phone #: ###-#### Internet Inspection Request from: Jamie Winters
ELE07-02299 Permanent Service8/9/20078/9/20078/9/2007 3:53:50 PMPFAIL
terry Phone #: ###-####
no SER allowed in conduit, needs 3/0 copper or 250KC mil for 400 amp feeder
support pvc
ELE07-02631 Electrical Rough-In8/9/20078/9/20078/9/2007 3:06:54 PMPPASS
rocky Note; ceiling grid Phone #: ###-####
ELE07-02771 Electrical Rough-In8/9/20078/9/20078/9/2007 2:17:42 PMPPASS
andy Phone #: ###-####
ELE07-02780 Permanent Service8/9/20078/9/20078/9/2007 1:30:24 PMPPASS
butch Phone #: ###-####
check water bonding on r/i
P/S O/H R Ok
ELE07-01881 Electrical Rough-In8/8/20078/9/20078/9/2007 12:15:52 PMAPART
rick Phone #: ###-#### - underground
underground ok
ELE07-01881 Rough-In Permanent Service8/8/20078/9/20078/9/2007 11:56:43 AMAPASS
rick Phone #: ###-####
R/I Ok
P/S U/G N Ok
ELE07-02707 Permanent Service8/8/20078/9/20078/9/2007 11:25:55 AMAPASS
final on new serivces,ANY QUESTIONS CALL gEORGE @###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose
ELE07-02707 Final8/9/20078/9/20078/9/2007 11:25:46 AMPPASS
final on new serivces,ANY QUESTIONS CALL gEORGE @###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose
ELE07-02382 Electrical Rough-In8/7/20078/9/20078/9/2007 10:51:56 AMAPASS
call shane for access please allow 10 to 15 minutes travel time. Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange
ELE07-02776 Conference8/8/20078/9/20078/9/2007 10:05:05 AMAPART
darren Phone #: ###-####
talked about remodel requirements
ELE07-02586 Conference8/8/20078/9/20078/9/2007 9:26:08 AMAPART
Phone #: ###-#### Internet Inspection Request from: Heather Packer
talkwed about service
ELE07-02777 Electrical Rough-In8/8/20078/9/20078/9/2007 8:53:16 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Thomas Marshall