FIR05-00536
| INSP-Sprinkler Rough-in | 8/8/2007 | 8/9/2007 | 8/10/2007 11:23:20 AM | A | PART |
|
|
OH fire sprinklers are good for cover at the east elevator lobby roulon ceiling 5th floor as circled on approved resubmittals.
|
FIR07-00650
| INSP-Sprinkler Rough-in/Hydro | 8/9/2007 | 8/9/2007 | 8/9/2007 5:06:46 PM | P | PART |
|
|
UG fire supply line installation appears acceptable, however no plans could be located on site for verification of design, need to provide correct documents at next inspection.
|
FIR07-00474
| INSP-Sprinkler Rough-in | 8/9/2007 | 8/9/2007 | 8/9/2007 4:20:59 PM | P | PART |
|
|
Begin 24 hr air testing at 45 psi.@4:00 pm.
|
FIR06-00011
| INSP-Alarm Testing | 8/9/2007 | 8/9/2007 | 8/9/2007 4:02:55 PM | P | DEFR |
|
|
See inspection comments per M. Timmerman.
|
FIR07-00668
| INSP-Sprinkler Rough-in | 8/8/2007 | 8/9/2007 | 8/9/2007 4:01:38 PM | P | PART |
|
|
OH fire sprinkler modifications are approved for cover, noted/okayed field changes at three areas due to wall layouts not indicated on plans.
|
FIR07-00627
| INSP-Final Inspection | 8/9/2007 | 8/9/2007 | 8/9/2007 3:34:13 PM | P | DEFR |
|
|
jodi Phone #: ###-####. Sam Rogers added: 8/9, 11:25am, I called Jodi at Mtn Alarm left voice message to call me at ###-#### to discuss the situation here; we won't make the inspection unitl we can discuss it with her.
|
BLD05-03359
| FIRE-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 3:32:54 PM | P | PASS |
|
|
c/n items complete, fire life safety finaled.
|
BLD07-01258
| FIRE-Final Inspection | 8/9/2007 | 8/9/2007 | 8/9/2007 3:03:16 PM | P | FAIL |
|
|
The exit sign and one emergency light at the west exit door do not function.
|
BLD07-01225
| FIRE-Conference | 8/9/2007 | 8/9/2007 | 8/9/2007 2:32:09 PM | P | DONE |
|
|
Discussion with contractor and structural inspector regarding concealed spaces at the exterior of the building.
|
BLD06-03339
| FIRE-Final Inspection | 8/9/2007 | 8/9/2007 | 8/9/2007 2:23:20 PM | P | NR |
|
|
Fire life safety inspection completed acceptable, final pending project related fire sprinkler permits FIR06-00959 and FIR07-00553.
|
FIR06-00959
| INSP-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 2:18:49 PM | P | PART |
|
|
Inspected remainder of permit scope work indicated on sheets FP 2.3.1, 2.2.4, 2.2.2, 2.2.3, and reinspection for items on 2.2.1. All areas are satisfactory with the exception of one missing head as noted on FP2.2.3.
|
FIR06-00934
| INSP-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 2:12:05 PM | P | PASS |
|
|
Final fire alarm inspection passed, permit finaled.
|
FIR06-00007
| INSP-Final Inspection | 8/7/2007 | 8/9/2007 | 8/9/2007 2:11:12 PM | A | DEFR |
|
|
No time to complete this inspection today, rescheduled as discussed.
|
FIR05-00524
| INSP-Conference | 8/6/2007 | 8/9/2007 | 8/9/2007 2:10:22 PM | A | DONE |
|
|
Discussion with contractor regarding cancellation of this permit.
|
FIR07-00529
| INSP-Final Inspection | 8/7/2007 | 8/9/2007 | 8/9/2007 2:08:18 PM | A | PASS |
|
|
Corrections verified for compliance, fire alarm permit finaled.
|
BLD06-02382
| FIRE-Final Inspection | 8/9/2007 | 8/9/2007 | 8/9/2007 11:00:47 AM | A | PASS |
|
|
Noted items at previous inspection are complete, final fire life safety passed.
|
FIR07-00530
| INSP-Sprinkler Rough-in | 8/8/2007 | 8/9/2007 | 8/9/2007 10:59:40 AM | | PASS |
|
|
Tenting corrections verified for completion, OH sprinkler piping is approved for cover. Changed to pass- for cover purposes - slr
|
BLD06-00908
| FIRE-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 10:58:02 AM | A | FAIL |
|
|
Threshold at unit 101prevents door closure from operating correctly, no access provided to unit 102 to complete inspection, 103 and 104 are acceptable.
|
BLD06-00909
| FIRE-Final Inspection | 8/8/2007 | 8/9/2007 | 8/9/2007 10:55:49 AM | A | PASS |
|
|
Fire life safety passed field inspection.
|