Inspections for the day of: Thursday, August 9, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00536 INSP-Sprinkler Rough-in8/8/20078/9/20078/10/2007 11:23:20 AMAPART
OH fire sprinklers are good for cover at the east elevator lobby roulon ceiling 5th floor as circled on approved resubmittals.
FIR07-00650 INSP-Sprinkler Rough-in/Hydro8/9/20078/9/20078/9/2007 5:06:46 PMPPART
UG fire supply line installation appears acceptable, however no plans could be located on site for verification of design, need to provide correct documents at next inspection.
FIR07-00474 INSP-Sprinkler Rough-in8/9/20078/9/20078/9/2007 4:20:59 PMPPART
Begin 24 hr air testing at 45 psi.@4:00 pm.
FIR06-00011 INSP-Alarm Testing8/9/20078/9/20078/9/2007 4:02:55 PMPDEFR
See inspection comments per M. Timmerman.
FIR07-00668 INSP-Sprinkler Rough-in8/8/20078/9/20078/9/2007 4:01:38 PMPPART
OH fire sprinkler modifications are approved for cover, noted/okayed field changes at three areas due to wall layouts not indicated on plans.
FIR07-00627 INSP-Final Inspection8/9/20078/9/20078/9/2007 3:34:13 PMPDEFR
jodi Phone #: ###-####. Sam Rogers added: 8/9, 11:25am, I called Jodi at Mtn Alarm left voice message to call me at ###-#### to discuss the situation here; we won't make the inspection unitl we can discuss it with her.
BLD05-03359 FIRE-Final Inspection8/8/20078/9/20078/9/2007 3:32:54 PMPPASS
c/n items complete, fire life safety finaled.
BLD07-01258 FIRE-Final Inspection8/9/20078/9/20078/9/2007 3:03:16 PMPFAIL
The exit sign and one emergency light at the west exit door do not function.
BLD07-01225 FIRE-Conference8/9/20078/9/20078/9/2007 2:32:09 PMPDONE
Discussion with contractor and structural inspector regarding concealed spaces at the exterior of the building.
BLD06-03339 FIRE-Final Inspection8/9/20078/9/20078/9/2007 2:23:20 PMPNR
Fire life safety inspection completed acceptable, final pending project related fire sprinkler permits FIR06-00959 and FIR07-00553.
FIR06-00959 INSP-Final Inspection8/8/20078/9/20078/9/2007 2:18:49 PMPPART
Inspected remainder of permit scope work indicated on sheets FP 2.3.1, 2.2.4, 2.2.2, 2.2.3, and reinspection for items on 2.2.1. All areas are satisfactory with the exception of one missing head as noted on FP2.2.3.
FIR06-00934 INSP-Final Inspection8/8/20078/9/20078/9/2007 2:12:05 PMPPASS
Final fire alarm inspection passed, permit finaled.
FIR06-00007 INSP-Final Inspection8/7/20078/9/20078/9/2007 2:11:12 PMADEFR
No time to complete this inspection today, rescheduled as discussed.
FIR05-00524 INSP-Conference8/6/20078/9/20078/9/2007 2:10:22 PMADONE
Discussion with contractor regarding cancellation of this permit.
FIR07-00529 INSP-Final Inspection8/7/20078/9/20078/9/2007 2:08:18 PMAPASS
Corrections verified for compliance, fire alarm permit finaled.
BLD06-02382 FIRE-Final Inspection8/9/20078/9/20078/9/2007 11:00:47 AMAPASS
Noted items at previous inspection are complete, final fire life safety passed.
FIR07-00530 INSP-Sprinkler Rough-in8/8/20078/9/20078/9/2007 10:59:40 AM PASS
Tenting corrections verified for completion, OH sprinkler piping is approved for cover. Changed to pass- for cover purposes - slr
BLD06-00908 FIRE-Final Inspection8/8/20078/9/20078/9/2007 10:58:02 AMAFAIL
Threshold at unit 101prevents door closure from operating correctly, no access provided to unit 102 to complete inspection, 103 and 104 are acceptable.
BLD06-00909 FIRE-Final Inspection8/8/20078/9/20078/9/2007 10:55:49 AMAPASS
Fire life safety passed field inspection.