Inspections for the day of: Monday, August 9, 2010.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00374 INSP-Sprinkler Rough-in8/9/20108/9/20108/10/2010 2:01:31 PMPPART
Okay to cover overhead work at two restrooms as marked on stamped plan set with today's date.
FIR10-00377 INSP-Sprinkler Rough-in8/9/20108/9/20108/9/2010 3:16:00 PMPPART
Overhead fire sprinkler modifications per the scope of work are approved for cover at the drop ceilings.
FIR10-00258 INSP-Final Inspection8/6/20108/9/20108/9/2010 3:14:37 PMPPART
Correction items verified for completion. Final pending project related fire alarm permit work.
FIR10-00256 INSP-Final Inspection8/6/20108/9/20108/9/2010 3:14:06 PMPPART
Correction items verified for completion. Final pending project related fire alarm permit work.
FIR10-00305 INSP-Final Inspection8/6/20108/9/20108/9/2010 3:12:50 PMPFAIL
Missing tamper switches at the fire sprinkler riser control valves as shown on approved plans and required per IFC 903.4. Notification appliance at the dining area is the incorrect cd setting, notification device at restroom 114 is not properly installed, provide signage at the FACP and riser room doors per review note # 28.
FIR10-00306 INSP-Final Inspection8/6/20108/9/20108/9/2010 3:10:47 PMPFAIL
Missing tamper switches at the fire sprinkler riser control valves as shown on approved plans and required per IFC 903.4. Notification appliance at the dining area is the incorrect cd setting, notification device at restroom 116 is not properly installed, provide signage at the FACP and riser room doors per review note # 28.
BLD10-01345 FIRE-Final Inspection8/9/20108/9/20108/9/2010 12:47:06 PMPPASS
Life safety finaled.
BLD10-01346 FIRE-Final Inspection8/9/20108/9/20108/9/2010 12:46:18 PMPPASS
Life safety inspection passed.
BLD10-00294 FIRE-Final Inspection8/6/20108/9/20108/9/2010 12:45:16 PMAPASS
Life safety is accpetable pending approved door hardware at the north exit- to be verified for compliance by the structural inspector. See red lined plan general notes items (K) and (L) for details.
BLD10-01717 FIRE-Final Inspection8/5/20108/9/20108/9/2010 12:41:55 PMAFAIL
Post the fire extinguisher, remove the manual thumbturn at the main entry/exit door and provide approved hardware and signage per permit documents, provide approved hardware at the south door or blank as discussed.