FIR10-00374
| INSP-Sprinkler Rough-in | 8/9/2010 | 8/9/2010 | 8/10/2010 2:01:31 PM | P | PART |
|
|
Okay to cover overhead work at two restrooms as marked on stamped plan set with today's date.
|
FIR10-00377
| INSP-Sprinkler Rough-in | 8/9/2010 | 8/9/2010 | 8/9/2010 3:16:00 PM | P | PART |
|
|
Overhead fire sprinkler modifications per the scope of work are approved for cover at the drop ceilings.
|
FIR10-00258
| INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 3:14:37 PM | P | PART |
|
|
Correction items verified for completion. Final pending project related fire alarm permit work.
|
FIR10-00256
| INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 3:14:06 PM | P | PART |
|
|
Correction items verified for completion. Final pending project related fire alarm permit work.
|
FIR10-00305
| INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 3:12:50 PM | P | FAIL |
|
|
Missing tamper switches at the fire sprinkler riser control valves as shown on approved plans and required per IFC 903.4. Notification appliance at the dining area is the incorrect cd setting, notification device at restroom 114 is not properly installed, provide signage at the FACP and riser room doors per review note # 28.
|
FIR10-00306
| INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 3:10:47 PM | P | FAIL |
|
|
Missing tamper switches at the fire sprinkler riser control valves as shown on approved plans and required per IFC 903.4. Notification appliance at the dining area is the incorrect cd setting, notification device at restroom 116 is not properly installed, provide signage at the FACP and riser room doors per review note # 28.
|
BLD10-01345
| FIRE-Final Inspection | 8/9/2010 | 8/9/2010 | 8/9/2010 12:47:06 PM | P | PASS |
|
|
Life safety finaled.
|
BLD10-01346
| FIRE-Final Inspection | 8/9/2010 | 8/9/2010 | 8/9/2010 12:46:18 PM | P | PASS |
|
|
Life safety inspection passed.
|
BLD10-00294
| FIRE-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 12:45:16 PM | A | PASS |
|
|
Life safety is accpetable pending approved door hardware at the north exit- to be verified for compliance by the structural inspector. See red lined plan general notes items (K) and (L) for details.
|
BLD10-01717
| FIRE-Final Inspection | 8/5/2010 | 8/9/2010 | 8/9/2010 12:41:55 PM | A | FAIL |
|
|
Post the fire extinguisher, remove the manual thumbturn at the main entry/exit door and provide approved hardware and signage per permit documents, provide approved hardware at the south door or blank as discussed.
|