MIS10-00226 FIR-Conference7/30/20108/4/2010 A 
follow up inspection
FIR10-00196 INSP-Final Inspection8/6/20108/9/20108/9/2010 3:25:22 PMPFAIL
There is a pendant head located in a basement closet that has been installed under 4" from a wall. I contacted Tim about the garage door in the basement storage room that is obstructing a single pendant head. Tim stated that he was alright with it.
FIR10-00302 INSP-Sprinkler Rough-in8/9/20108/9/20108/9/2010 2:59:33 PMPFAIL
Sizing, placement and hangers for the new sprinkler piping was inspected and passed. The locations of the earthquake bracing does not match plans and in some locations the two way and four way braces are in switched locations. Also the maximum storage height is listed as 16'-0" but the storage is up to 19'-6" in several locations. Also no fire alarm permit has been applied/issued for the tamper switches and flow switches. This fire sprinkler permit will not be finaled until an alarm permit has been applied for. A forward flush test was not performed due to the design possibly being changed due to the new storage height. An above ground hydro test will not be required.
BLD10-01329 FIRE-Final Inspection8/6/20108/9/20108/9/2010 2:18:00 PMAPASS
Life safety passed