MIS10-00226
| FIR-Conference | 7/30/2010 | 8/4/2010 | | A | |
|
|
follow up inspection
|
FIR10-00196
| INSP-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 3:25:22 PM | P | FAIL |
|
|
There is a pendant head located in a basement closet that has been installed under 4" from a wall. I contacted Tim about the garage door in the basement storage room that is obstructing a single pendant head. Tim stated that he was alright with it.
|
FIR10-00302
| INSP-Sprinkler Rough-in | 8/9/2010 | 8/9/2010 | 8/9/2010 2:59:33 PM | P | FAIL |
|
|
Sizing, placement and hangers for the new sprinkler piping was inspected and passed. The locations of the earthquake bracing does not match plans and in some locations the two way and four way braces are in switched locations. Also the maximum storage height is listed as 16'-0" but the storage is up to 19'-6" in several locations. Also no fire alarm permit has been applied/issued for the tamper switches and flow switches. This fire sprinkler permit will not be finaled until an alarm permit has been applied for. A forward flush test was not performed due to the design possibly being changed due to the new storage height. An above ground hydro test will not be required.
|
BLD10-01329
| FIRE-Final Inspection | 8/6/2010 | 8/9/2010 | 8/9/2010 2:18:00 PM | A | PASS |
|
|
Life safety passed
|