FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 8/9/2011 | 8/9/2011 | 8/10/2011 3:45:06 PM | P | PART |
|
|
Completed hydrostatic testing of both building #2 and building #3 1st floor antifreeze systems.
|
FIR11-00026
| INSP-Final Inspection | 8/8/2011 | 8/9/2011 | 8/9/2011 5:41:31 PM | A | FAIL |
|
|
Noted items during initial walkthrough include 1st floor- provide WP notification devices at shower 140 and unisex 117, notification at study rooms 119A and 119B are overspaced, noted two added ID at store room 115 not shown on plans. 2nd floor- provide signage at the FACP room, install a SD at the panel room, TS, PS and FS at the preaction riser are not shown on plans, hall 212A and 212B notification devices are overspaced/obstructed, IT tech room A/V is overspaced. 3rd floor- casual seating area lacks visual coverage, hall 345 is overspaced. Provide record of inspection and testing including a list of signals per fire code review notes. See also items # 2,3, 7, and 33 on review comments. Post accurate map at the panel. Field modifications including two additional ID, 14 relay modules for AHU shutdown, 4 fire sprinkler monitor modules, and 3 DH to be shown on resubmital plans and matrix as discussed.
|
BLD11-00969
| FIRE-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:25:12 PM | P | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
FIR11-00385
| INSP-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:22:57 PM | P | PASS |
|
|
Scope of fire alarm work completed. Permit final approved.
|
FIR10-00540
| INSP-Final Inspection | 8/4/2011 | 8/9/2011 | 8/9/2011 5:20:35 PM | A | NR |
|
|
|
BLD10-01578
| FIRE-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:20:03 PM | P | PASS |
|
|
Fire life safety final inspection passed.
|
BLD10-01036
| FIRE-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:19:28 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
BLD11-00483
| FIRE-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:18:30 PM | P | FAIL |
|
|
C/N items include; provide one extinguisher at the mechanical room, missing EM lighting at the excercise room, repair exit signs and EM lights at the adjacent exit access. Refer to plan sheet key notes for details and red line annotations.
|
FIR11-00308
| INSP-Sprinkler Rough-in/Hydro | 8/8/2011 | 8/9/2011 | 8/9/2011 5:09:47 PM | A | PART |
|
|
Overhead hydrostatic testing for the new dry system piping passed. Discussed schedule for pneumatic test.
|
FIR11-00039
| INSP-Final Inspection | 8/8/2011 | 8/9/2011 | 8/9/2011 5:07:56 PM | A | PASS |
|
|
Reinspection passed. Fire alarm permit finaled.
|
FIR11-00038
| INSP-Final Inspection | 8/8/2011 | 8/9/2011 | 8/9/2011 5:05:37 PM | A | PASS |
|
|
Reinspection for noted correction items passed. Fire alarm permit finaled.
|
BLD11-01511
| FIRE-Final Inspection | 8/8/2011 | 8/9/2011 | 8/9/2011 5:03:26 PM | A | PASS |
|
|
Reinspection for noted correction items passed.
|
FIR11-00197
| INSP-Final Inspection | 8/1/2011 | 8/9/2011 | 8/9/2011 5:02:08 PM | A | PASS |
|
|
Fire alarm work passed after hours re-inspection. Permit finaled.
|
FIR11-00180
| INSP-Final Inspection | 8/9/2011 | 8/9/2011 | 8/9/2011 5:01:01 PM | A | PASS |
|
|
Fire sprinkler permit passed final inspection.
|