Inspections for the day of: Friday, August 9, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01969 Conference8/9/20138/9/20138/9/2013 2:52:05 PMPDONE
Call John @ ###-#### for questions Phone #: ###-#### >> Inspection requested via web by John Edwards talked about field evaluation of equipment, UL508 panels, motors not listed
ELE13-02137 Permanent Service8/9/20138/9/20138/9/2013 2:41:46 PMPFAIL
call 20 min prior to meet//to turn on service// Ann Phone #: ###-#### met owners, 2 services on building, separated, illegal sub-panel, service on main house built in by living area such that service entrance too far in building, breakers gone and would be open bus, need to set up as duplex and provide mains and sub-panels out of meter-pak
ELE13-01836 Final8/9/20138/9/20138/9/2013 2:06:06 PMPPASS
ceiling insp & final - tim Phone #: ###-#### ok cover ceiling, ok final, signed card
ELE13-02012 Final8/9/20138/9/20138/9/2013 1:45:49 PMPPASS
Wall cover. Danny on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen ok cover south wall only
ELE13-02103 Final8/9/20138/9/20138/9/2013 12:48:52 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Matthew White see ri
ELE13-02103 Electrical Rough-In8/9/20138/9/20138/9/2013 12:09:51 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Matthew White ri ok, will do final later
ELE13-02040 Final8/8/20138/9/20138/9/2013 11:53:07 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Jesse Fuentes ok final
ELE13-00644 Final8/8/20138/9/20138/9/2013 10:33:24 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman corrections made, ok final
ELE13-02129 Electrical Rough-In8/8/20138/9/20138/9/2013 10:16:25 AMAPASS
please call prior so I can make sure you can get in. Phone #: ###-#### >> Inspection requested via web by Brian Hughes walls only ok cover
ELE13-01492 Electrical Rough-In8/8/20138/9/20138/9/2013 9:57:54 AMAFAIL
Front door will be open Phone #: ###-#### >> Inspection requested via web by shane miller called, left message, shall provide nailplates, ground metal boxes, 1 1/4" for nm cable on studs, staple nm cable out of box, jacketing shall be minimum 1/4" in box, attic access shall protect cable within 6' of access
ELE13-00673 Final8/8/20138/9/20138/9/2013 9:07:59 AMAPART
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden 1st floor ok, need to install equipment, signed t/o card
ELE13-02125 Electrical Rough-In8/8/20138/9/20138/9/2013 8:23:54 AMAPASS
Please Call Dan 1 hr. before inspection Phone #: ###-#### >> Inspection requested via web by Dan Rohl ri ok, 2 baths
ELE13-01010 Final8/8/20138/9/20138/9/2013 7:54:11 AMAPASS
Garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas ok final