ELE13-01969
| Conference | 8/9/2013 | 8/9/2013 | 8/9/2013 2:52:05 PM | P | DONE |
|
|
Call John @ ###-#### for questions Phone #: ###-#### >> Inspection requested via web by John Edwards talked about field evaluation of equipment, UL508 panels, motors not listed
|
ELE13-02137
| Permanent Service | 8/9/2013 | 8/9/2013 | 8/9/2013 2:41:46 PM | P | FAIL |
|
|
call 20 min prior to meet//to turn on service// Ann Phone #: ###-#### met owners, 2 services on building, separated, illegal sub-panel, service on main house built in by living area such that service entrance too far in building, breakers gone and would be open bus, need to set up as duplex and provide mains and sub-panels out of meter-pak
|
ELE13-01836
| Final | 8/9/2013 | 8/9/2013 | 8/9/2013 2:06:06 PM | P | PASS |
|
|
ceiling insp & final - tim Phone #: ###-#### ok cover ceiling, ok final, signed card
|
ELE13-02012
| Final | 8/9/2013 | 8/9/2013 | 8/9/2013 1:45:49 PM | P | PASS |
|
|
Wall cover. Danny on site Phone #: ###-#### >> Inspection requested via web by Buster Bowen ok cover south wall only
|
ELE13-02103
| Final | 8/9/2013 | 8/9/2013 | 8/9/2013 12:48:52 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White see ri
|
ELE13-02103
| Electrical Rough-In | 8/9/2013 | 8/9/2013 | 8/9/2013 12:09:51 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White ri ok, will do final later
|
ELE13-02040
| Final | 8/8/2013 | 8/9/2013 | 8/9/2013 11:53:07 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Jesse Fuentes ok final
|
ELE13-00644
| Final | 8/8/2013 | 8/9/2013 | 8/9/2013 10:33:24 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Emmet Bushman corrections made, ok final
|
ELE13-02129
| Electrical Rough-In | 8/8/2013 | 8/9/2013 | 8/9/2013 10:16:25 AM | A | PASS |
|
|
please call prior so I can make sure you can get in. Phone #: ###-#### >> Inspection requested via web by Brian Hughes walls only ok cover
|
ELE13-01492
| Electrical Rough-In | 8/8/2013 | 8/9/2013 | 8/9/2013 9:57:54 AM | A | FAIL |
|
|
Front door will be open Phone #: ###-#### >> Inspection requested via web by shane miller called, left message, shall provide nailplates, ground metal boxes, 1 1/4" for nm cable on studs, staple nm cable out of box, jacketing shall be minimum 1/4" in box, attic access shall protect cable within 6' of access
|
ELE13-00673
| Final | 8/8/2013 | 8/9/2013 | 8/9/2013 9:07:59 AM | A | PART |
|
|
Contact: Garrett Collins Phone #: ###-#### >> Inspection requested via web by Deb Gooden 1st floor ok, need to install equipment, signed t/o card
|
ELE13-02125
| Electrical Rough-In | 8/8/2013 | 8/9/2013 | 8/9/2013 8:23:54 AM | A | PASS |
|
|
Please Call Dan 1 hr. before inspection Phone #: ###-#### >> Inspection requested via web by Dan Rohl ri ok, 2 baths
|
ELE13-01010
| Final | 8/8/2013 | 8/9/2013 | 8/9/2013 7:54:11 AM | A | PASS |
|
|
Garage code 0243 Phone #: ###-#### >> Inspection requested via web by Heath Thomas ok final
|