ELE13-01373
| ELE-Aging Inspection | 8/9/2016 | 8/9/2016 | 8/12/2016 8:00:34 AM | | CANC |
|
|
too busy
|
ELE13-00256
| Final | 8/9/2016 | 8/9/2016 | 8/9/2016 2:43:04 PM | P | CANC |
|
|
Ryan Phone #: ###-#### not ready for final exposed romex will be be gaurded and all devices put in place, not meter was installed at this time, will clone a p/s only at this time
|
ELE13-00256
| Permanent Service | 8/9/2016 | 8/9/2016 | 8/9/2016 2:42:47 PM | P | PASS |
|
|
Ryan Phone #: ###-#### p/s o/h n ok
|
ELE16-02574
| Conference | 8/8/2016 | 8/9/2016 | 8/9/2016 2:12:21 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Cindie Swaim
|
ELE16-02155
| Electrical Rough-In | 8/9/2016 | 8/9/2016 | 8/9/2016 2:04:49 PM | P | CANC |
|
|
Inspection requested via web by CHRIS CARMINE wrong day called in
|
ELE16-02558
| Electrical Rough-In | 8/8/2016 | 8/9/2016 | 8/9/2016 1:42:31 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Cheryle Fleshman only added wall in bath. receptacle was existing and wall was not touched therefor it was not upgraded nor required to be 20 amp. Switch wall only ok cover
|
ELE16-02573
| Final | 8/8/2016 | 8/9/2016 | 8/9/2016 12:50:59 PM | A | CANC |
|
|
Power off for more than 1 year. For access contact Brian Keeley at ###-#### Phone #: ###-#### Inspection requested via web by steve ragan needed p/s
|
ELE16-02573
| Permanent Service | 8/9/2016 | 8/9/2016 | 8/9/2016 12:48:43 PM | P | PASS |
|
|
Power off for more than 1 year. For access contact Brian Keeley at ###-#### Phone #: ###-#### Inspection requested via web by steve ragan check for cover j-box under trailer for final p/s u/g rec ok
|
ELE16-02513
| Electrical Rough-In | 8/9/2016 | 8/9/2016 | 8/9/2016 12:17:03 PM | P | CANC |
|
|
ceiling, call ahead for access; Rick Phone #: ###-#### parcel tag note stated sewer impact fees needed to be paid before inspections
|
ELE16-01234
| Electrical Rough-In | 8/9/2016 | 8/9/2016 | 8/9/2016 12:15:39 PM | P | PASS |
|
|
Underground. Shannon is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates underground for sign ok
|
ELE16-00867
| Final | 8/8/2016 | 8/9/2016 | 8/9/2016 11:40:28 AM | A | PASS |
|
|
Please provide a final inspection at the Buffalo Wild Wings TI. Rod with Steed Construction should be on site and will be your contact there. His number is ###-####. Phone #: ###-#### Inspection requested via web by Kevin Perez as per rock hudson all other areas were fine. correction fixed, installed GFCI breakers for bar area. final ok.
|
ELE16-02430
| Electrical Rough-In | 8/8/2016 | 8/9/2016 | 8/9/2016 10:59:04 AM | A | FAIL |
|
|
Please call Kaden (###-####) before going to property so he can arrange access into the home. Phone #: ###-#### Inspection requested via web by William Salts 300.4 Bored holes within 1 1/4" from edge of framing memeber shall have nailplate installed 210.63 shall have a receptacle located within 25' of air conditioning equiptment(EC stated he will add outlet in bottom of service for final) 314.17 type NM cable shall be supported within 8" of a box 110.26 area below panel is dedicated for electrical space remove phone de-mark 334.12 Typw NM cable shall not be used in wet locations
|
ELE16-01537
| Electrical Rough-In | 8/9/2016 | 8/9/2016 | 8/9/2016 9:59:24 AM | A | PASS |
|
|
Trench Phone #: ###-#### Inspection requested via web by mike brown underground on west end of parking lot ok cover east end will be done when trenched.
|
ELE16-02497
| Rough-In Permanent Service | 8/9/2016 | 8/9/2016 | 8/9/2016 9:11:37 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn rough-in ok p/s u/g n ok
|
ELE16-02585
| Final | 8/8/2016 | 8/9/2016 | 8/9/2016 9:10:52 AM | A | PASS |
|
|
This is a service off more than a year inspection. There is a keylock located on the gas meter on the right side of the house. The code is 3632 Phone #: ###-#### Inspection requested via web by Ryan Wake p/s u/g rec ok
|
ELE16-02452
| Final | 8/8/2016 | 8/9/2016 | 8/9/2016 8:25:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg final for pedestal hook up ok
|
ELE16-02558
| Final | 8/8/2016 | 8/9/2016 | 8/8/2016 5:19:20 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Cheryle Fleshman Inspection cancelled from web by: Cheryle Fleshman
|