FIR15-00892
| INSP-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 11:11:41 AM | P | FAIL |
|
|
Todays inspection wsa just to verify the forward flush which passed.
|
BLD15-00516
| FIRE-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 10:29:34 AM | A | PART |
|
|
Pending approval of other trade inspection groups; a temporary occupancy is ok for life safety with Scott's permission. I need the project related fire alarm and fire sprinkler permits addressed, a permanant address, riser room signage, the swimming pool permit finaled, occupant load sign and door hardware for pool area installed.
|
FIR16-00087
| INSP-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 10:28:18 AM | A | PART |
|
|
A temporary occupancy is ok for life safety with Scott's permission. I need as-builts, testing of elevator car #1 and the map at the facp.
|
FIR15-00709
| INSP-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 10:27:04 AM | A | PART |
|
|
A temporary occupancy is ok for life safety with Scott's permission. I need as-builts, replace head in Room 105 and the exposed plastic pipe in the east stair well corrected.
|
BLD16-00129
| FIRE-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 10:24:31 AM | A | FAIL |
|
|
Remove the thumbturn from the main entry exit and provide sticker as discussed, provide fire extinguisher on the upper level, repair the exit sign at the main exit, install all door hardware, provide correct address and suite number.
Shane Phone #: ###-####
|
FIR16-00517
| INSP-Final Inspection | 8/8/2016 | 8/9/2016 | 8/9/2016 10:22:47 AM | A | FAIL |
|
|
I called the contact phone number there was no answer and the voice mail box was full. I then went to the job site but the only contact was the restraunt manager but he had no city approved plans. No inspection was performed.
Steven Vaughn is point of Contact. They are open for lunch at 11:00AM. Earlier is better. Phone #: ###-#### Inspection requested via web by Randy Knutson
|