Inspections for the day of: Wednesday, August 9, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02600 FIRE-Final Inspection8/8/20178/9/20178/9/2017 3:31:56 PMPCANC
Jill Phone #: ###-####
BLD16-00124 FIRE-Final Inspection8/9/20178/9/20178/9/2017 3:30:24 PMPPASS
life safety passed. No gates/fence has been installed betwee building 1 and 2
BLD17-02603 FIRE-Final Inspection8/8/20178/9/20178/9/2017 2:21:21 PMPFAIL
Paint address as discussed, provide re-certification for both hood suppression systems and provide ABC extinguisher for kitchen area and repair the emergency light at the front counter
FIR16-00821 INSP-Sprinkler Rough-in8/9/20178/9/20178/9/2017 1:49:46 PMPPASS
Piping rough-in for the center building (100) passed. Piping can not be covered until insulation has been verifed in all combustible concealed spaced.

Mikael Phone #: ###-####
FIR17-00392 INSP-Final Inspection8/8/20178/9/20178/9/2017 1:45:41 PMPFAIL
Provide correct heat detector spacing as per NFPA 72, provide separate point for PIV, provide correct account address, may need two additional manual pull stations ( I will follow up)
BLD17-01710 FIRE-Final Inspection8/8/20178/9/20178/9/2017 1:43:25 PMPFAIL
Need project related fire alrm permit finaled, provide sign for Riser Room and mount the third fire extinguisher as discussed.
FIR17-00424 INSP-Final Inspection8/8/20178/9/20178/9/2017 1:40:49 PMPPASS
Permit finaled
BLD17-02686 FIRE-Final Inspection8/8/20178/9/20178/9/2017 10:17:48 AMAFAIL
Remove the thumbturn dead bolt from the main exit (keyed ok), remove the thumbturn dead bolt from the Storage Room exit, provide two fire extinguishers as discussed. repair the two exit signs/emergency lights. There was an issue with an address but that has been worked out and a new address is now required.
FIR17-00345 INSP-Final Inspection8/3/20178/9/20178/9/2017 10:14:15 AMACANC
MIKE OSWALD
TO COINCIDE WITH FIRE LIFE SAFETY FINAL. Phone #: ###-#### Inspection requested via web by Brodie Stenquist
FIR17-00346 INSP-Sprinkler Rough-in8/8/20178/9/20178/9/2017 8:00:14 AMAPASS
Remaining sprinkler piping is ok to cover