BLD17-02600
| FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 3:31:56 PM | P | CANC |
|
|
Jill Phone #: ###-####
|
BLD16-00124
| FIRE-Final Inspection | 8/9/2017 | 8/9/2017 | 8/9/2017 3:30:24 PM | P | PASS |
|
|
life safety passed. No gates/fence has been installed betwee building 1 and 2
|
BLD17-02603
| FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 2:21:21 PM | P | FAIL |
|
|
Paint address as discussed, provide re-certification for both hood suppression systems and provide ABC extinguisher for kitchen area and repair the emergency light at the front counter
|
FIR16-00821
| INSP-Sprinkler Rough-in | 8/9/2017 | 8/9/2017 | 8/9/2017 1:49:46 PM | P | PASS |
|
|
Piping rough-in for the center building (100) passed. Piping can not be covered until insulation has been verifed in all combustible concealed spaced.
Mikael Phone #: ###-####
|
FIR17-00392
| INSP-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 1:45:41 PM | P | FAIL |
|
|
Provide correct heat detector spacing as per NFPA 72, provide separate point for PIV, provide correct account address, may need two additional manual pull stations ( I will follow up)
|
BLD17-01710
| FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 1:43:25 PM | P | FAIL |
|
|
Need project related fire alrm permit finaled, provide sign for Riser Room and mount the third fire extinguisher as discussed.
|
FIR17-00424
| INSP-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 1:40:49 PM | P | PASS |
|
|
Permit finaled
|
BLD17-02686
| FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 10:17:48 AM | A | FAIL |
|
|
Remove the thumbturn dead bolt from the main exit (keyed ok), remove the thumbturn dead bolt from the Storage Room exit, provide two fire extinguishers as discussed. repair the two exit signs/emergency lights. There was an issue with an address but that has been worked out and a new address is now required.
|
FIR17-00345
| INSP-Final Inspection | 8/3/2017 | 8/9/2017 | 8/9/2017 10:14:15 AM | A | CANC |
|
|
MIKE OSWALD TO COINCIDE WITH FIRE LIFE SAFETY FINAL. Phone #: ###-#### Inspection requested via web by Brodie Stenquist
|
FIR17-00346
| INSP-Sprinkler Rough-in | 8/8/2017 | 8/9/2017 | 8/9/2017 8:00:14 AM | A | PASS |
|
|
Remaining sprinkler piping is ok to cover
|