FIR16-00763
| INSP-Sprinkler Rough-in | 8/8/2017 | 8/9/2017 | 8/10/2017 4:16:45 PM | A | CANC |
|
|
Inspection request was for FIR16-00698, this inspection request is cancelled.
|
NAF17-00049
| INSP-Final | 8/9/2017 | 8/9/2017 | 8/9/2017 3:01:08 PM | P | DONE |
|
|
No fire sprinklers, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags, knox box is mounted on the northeast side of building. Final life fire safety inspection for area of work passed/complete.
|
FIR16-00586
| INSP-Sprinkler Rough-in | 8/9/2017 | 8/9/2017 | 8/9/2017 2:25:40 PM | P | PART |
|
|
Rough to cover inspection for south side of elevator lobby, level 4 overhead fire sprinkler piping/pendant heads complete, inspected area on level 4 approved for cover, north of elevator to be completed/inspected at a later date. Rough in inspection for south side level 5 complete, cover is not approved until insulation is installed over piping and passed inspection. North side of elevator on level 5 to be completed/inspected at a later date.
|
BLD17-01546
| FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 1:24:54 PM | P | CANC |
|
|
Inspection request cancelled, space not ready for final life fire safety inspection, office spaces are missing the ceiling tile, ceiling tile provides heat collection for fire sprinkler head operation. Inspection request will be made when ceiling tile is installed and complete.
|
FIR17-00296
| INSP-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 1:21:24 PM | P | PASS |
|
|
Rough in inspection complete for overhead fire sprinkler piping/pendant heads, approved for cover. Final fire sprinkler inspection passed/complete.
|
FIR17-00173
| INSP-Sprinkler Rough-in | 8/7/2017 | 8/9/2017 | 8/9/2017 10:42:58 AM | A | PART |
|
|
Tenting inspection complete, insulating contractor needs to provide documentation for the foam blow in insulation for compatibility with CPVC, cover is approved at builders discretion based on compatability report, if blow in insulation is not compatible then foam covered fire sprinkler piping will need to be replaced.
|