Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00486 INSP-Sprinkler Rough-in8/9/20188/9/20188/9/2018 1:14:47 PMPPASS
Tenting inspectin complete, all plastic sheeting was in place at time of inspection, all overhead fire sprinkler piping approved for cover.

Tenting inspection, call Anthony if there are any concerns. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR18-00273 INSP-Final Inspection8/8/20188/9/20188/9/2018 1:01:08 PMAPASS
Notes for as builts are entered under the FIR permit, final inspection complete.

Submitted as built plans to Lee Meredith, plans were approved after Troy left for the day. Scheduled new Inspection per Troy for approval. If there are questions please call Chris @ ###-####697 Phone #: ###-#### Inspection requested via web by Chris Siewert
BLD17-04166 FIRE-Final Inspection8/9/20188/9/20188/9/2018 12:59:21 PMPPASS
Previoulsy noted items have been completed, hood is acceptable without fire system based on site survey performed by Fire Experts, the closed type pizza oven does not require a fire system based on his survey. Final life fire safety inspection complete.

Rich Phone #: ###-####
BLD18-00392 FIRE-Final Inspection8/8/20188/9/20188/9/2018 12:40:55 PMAPASS
Previously noted items have been completed, final life fire safety inspection complete.

Please call ahead for lock code // chris Phone #: ###-####
NAF17-00064 INSP-Final8/9/20188/9/20188/9/2018 11:39:55 AMPDONE
Previously noted items have been completed, final life fire safety inspection complete. Gate between school and boys and girls clubs to be getting standard gate hardware per conversation with project superintendent, not an access control gate. If access control is installed on gate then access control will need to be connected to a fire alarm system and release on general fire alarm.



Call prior to going Phone #: 2089602639 >> Inspection requested via mobile web by Kevin hess
FIR18-00500 INSP-Final Inspection8/8/20188/9/20188/9/2018 11:08:57 AMACANC
Hood system not interfaced with the fire alarm panel per conversation with point of contact, he requested that the inspection request be cancelled.

Inspection requested via web by Don Kartchner
NAF18-00061 INSP-Sprinkler Rough-in8/8/20188/9/20188/9/2018 11:06:16 AMAPART
Rough to cover inspection for overhead fire sprinkler piping inn the commons area soffits complete, approved for cover.

rough in for common areas Phone #: ###-#### Inspection requested via web by Matthew Lewis
NAF18-00048 INSP-Sprinkler Rough-in/Hydro8/8/20188/9/20188/9/2018 11:05:13 AMADONE
Hydrostatic test for unerground supply witnessed, no pressure loss observed at riser provided gauge.

Phone #: ###-#### Inspection requested via web by Matthew Lewis
BLD18-01995 FIRE-Final Inspection8/8/20188/9/20188/9/2018 10:33:34 AMACANC
Discussed the issue about the outstanding FIR permit for the address with the point of contact, life fire safety inspection for C of O cannot be completed until outstanding FIR permit issue is resolved, this inspection is cancelled per conversation with point of contact.

Richard Phone #: ###-####
FIR18-00433 INSP-Final Inspection8/9/20188/9/20188/9/2018 10:18:29 AMACANC
Cancelled per conversation with point of contact.

Phone #: ###-#### Inspection requested via web by david davis
FIR17-00745 INSP-Final Inspection8/8/20188/9/20188/9/2018 10:17:57 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00371 INSP-Final Inspection8/8/20188/9/20188/9/2018 10:17:35 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00368 INSP-Final Inspection8/8/20188/9/20188/9/2018 10:17:16 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00370 INSP-Final Inspection8/8/20188/9/20188/9/2018 10:16:39 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00434 INSP-Final Inspection8/9/20188/9/20188/9/2018 10:16:13 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR17-00561 INSP-Final Inspection8/8/20188/9/20188/9/2018 10:15:44 AMAPASS
Final fire alarm inspection for area of work complete.

Please call 1/2 hour before arriving. Thanks Phone #: ###-#### Inspection requested via web by david davis
FIR18-00119 INSP-Sprinkler Rough-in8/8/20188/9/20188/9/2018 8:33:25 AMAFAIL
Drawings on site are not city approved drawings, could not find the city stap. Head in main entry is blocked, head needs relocated. Add head under mid level stairs. Numerous heads throughout are overspaced, as stated in permit description max spacing is 18ft by 18ft. Re-route piping that is bent around HVAC flex-duct located in basement level.

Contact Brad Westbrook ###-#### 30 min before RTC Start please, if voice mailbox is full please contact Leroy Anderson ###-#### please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
NAF18-00013 INSP-Final8/8/20188/9/20188/9/2018 7:31:38 AMADONE
Final fire alarm inspection complete.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
NAF18-00060 INSP-Final8/8/20188/9/20188/9/2018 7:30:06 AMAPART
Final fire alarm inspection complete for activation and visual inspection, as noted in last inspection as builts will be required to be submitted before final can be completed.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
FIR18-00433 INSP-Final Inspection8/8/20188/9/20188/9/2018 7:17:39 AMACANC
Please call 1/2 hour before arriving. Thanks Phone #: ###-#### >> Inspection requested via web by david davis Inspection cancelled from web by: david davis