Inspections for the day of: Wednesday, September 1, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00462 INSP-Sprinkler Rough-in9/1/20049/1/20049/1/2004 12:00:00 AM PASS
Sprinkler piping is ok to cover 9/1/2004 3:22:39 PM
FIR04-00236 INSP-Sprinkler Rough-in/Hydro8/30/20049/1/20049/1/2004 12:00:00 AMAFAIL
Not all of the hangers have been removed from the cross webbing of the trusses. In one location the hanger attachment is not scewed all the way into the truss 9/1/2004 10:10:58 AM
FIR04-00207 INSP-Final Inspection8/31/20049/1/20049/1/2004 12:00:00 AMPFAIL
Sprinkler heads installed are glass bulb type. Sprinkler heads submitted are link type. Resubmitt heads or install correct heads. 9/1/2004 2:05:08 PM
FIR04-00426 INSP-Final Inspection8/26/20049/1/20049/1/2004 12:00:00 AMPPASS
Permit finaled 9/1/2004 1:32:03 PM
FIR04-00439 INSP-Final Inspection9/1/20049/1/20049/1/2004 12:00:00 AMPPASS
Permit finaled
FIR04-00561 INSP-Conference9/1/20049/1/20049/1/2004 12:00:00 AMPDONE
Building contractor called wanting to know if I could do anything to speed up the review. I told him no and relayed the job history to him such as review and resubmittal dates to him.
FIR04-00207 INSP-Final Inspection8/30/20049/1/20048/31/2004 2:40:22 PMACANC
Contact; Brian - would like inspection around 8:30am, please call Brian to confirm.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley