ELE05-03206
| Temporary Service | 9/1/2005 | 9/1/2005 | 9/1/2005 4:29:46 PM | P | PASS |
|
|
darrell-- ###-#### called contr to rotate pole for clearance, add abrasion protection. t/s u/g n ok
|
ELE05-03203
| Rough-In Permanent Service | 9/1/2005 | 9/1/2005 | 9/1/2005 4:28:00 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called contr to add recpt in mbr, ric ok, p/s u/g n ok
|
ELE05-03189
| Permanent Service | 9/1/2005 | 9/1/2005 | 9/1/2005 1:54:52 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 7:14:18 AM. Contact: ###-####. p/s u/g n ok
|
ELE05-03143
| Permanent Service | 9/1/2005 | 9/1/2005 | 9/1/2005 1:52:41 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 7:09:06 AM. Contact: ###-####. p/s u/g n ok
|
ELE05-03188
| Permanent Service | 9/1/2005 | 9/1/2005 | 9/1/2005 1:51:45 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 9/1/2005 at 7:11:40 AM. Contact: ###-####. p/s u/g n ok NOTE: 5 meters for this permit.
|
ELE05-02451
| Final | 9/1/2005 | 9/1/2005 | 9/1/2005 1:07:01 PM | P | FAIL |
|
|
Equipment hook-up complete, ready for final. please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called contr, left corr notice, 110.3(A)(1) equip shall be suitable for installation,110.2 equip shall be approved, 110.26 space about equipment shall be maintained, 250.104 metal water piping shall be bonded
|
ELE05-03195
| Electrical Rough-In | 9/1/2005 | 9/1/2005 | 9/1/2005 12:41:23 PM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa callede contr, left corr notice, 330.30(B) mc cable shall be supported within 12" of box, 110.22 identification shall be provided for service, bldg space, and sub-panel,110.26(A)(2),(3) work space and height shall be provided for a/c equip.
|
ELE05-01228
| Final | 8/31/2005 | 9/1/2005 | 9/1/2005 10:28:38 AM | A | PASS |
|
|
Doug has left on vacation, please call the office if there are any problems. Thanks; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot corrections made, no access to panel to affix yellow sticker. ok to final
|
ELE05-03151
| Electrical Rough-In | 8/31/2005 | 9/1/2005 | 9/1/2005 10:27:19 AM | A | PASS |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok to final
|
ELE05-02589
| Rough-In Permanent Service | 8/31/2005 | 9/1/2005 | 9/1/2005 9:32:49 AM | A | DONE |
|
|
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy already done, looked at riser and ready for contr to call power co.
|
ELE05-03162
| Final | 8/31/2005 | 9/1/2005 | 9/1/2005 9:27:39 AM | A | PASS |
|
|
receptacle has been replaced with a GFCI receptacle and it is being fed from load side of a fuse. Thanks Bob!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE04-02639
| Electrical Rough-In | 8/31/2005 | 9/1/2005 | 9/1/2005 9:08:01 AM | A | PART |
|
|
ceiling insp. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer clg cover ok, see dwg, ok for covers in elect room
|
ELE05-03181
| Temporary Service | 8/31/2005 | 9/1/2005 | 9/1/2005 8:15:57 AM | A | FAIL |
|
|
###-#### steve called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts
|
ELE05-01630
| Rough-In Permanent Service | 8/31/2005 | 9/1/2005 | 9/1/2005 8:12:54 AM | A | PART |
|
|
PARTIAL ROUGH IN; Phone #: ###-#### Internet Inspection Request from: Nikki Day north 1/2 walls only ok to cover and all soffits ok to cover
|