FIR05-00209
| INSP-Final Inspection | 8/30/2005 | 8/31/2005 | | A | |
|
|
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.
|
FIR05-00186
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 5:52:30 PM | A | PART |
|
|
Completed testing of all devices and re-tested defficient items. All issues are satisfactory except the outside bell at Fred Meyers and Mongolian Bistro failed to function properly.
|
BLD05-01345
| FIRE-Alarm Testing | 8/31/2005 | 9/1/2005 | 9/1/2005 5:11:29 PM | P | FAIL |
|
|
This inspection was for the fire alarm which was not completed yet.
|
BLD05-01345
| FIRE-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 5:05:11 PM | P | FAIL |
|
|
Provide signage for fire lane, provide directional arrows on exit signs in hall, test and final fire alarm prior to life safety sign off.
|
BLD04-01823
| FIRE-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 4:58:00 PM | P | PASS |
|
|
Shell fire safety passed inspection.
|
MIS05-00123
| FIR-Final | 9/1/2005 | 9/1/2005 | 9/1/2005 4:25:24 PM | P | FAIL |
|
|
Provide current annual inspection tag for fire extinguisher and lower mounting height to no higher than 48" to the handle AFF.
|
FIR05-00394
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 3:29:02 PM | A | DEFR |
|
|
This inspection to be performed by Mary Froemke due to scheduling conflicts.
|
FIR05-00267
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 3:22:23 PM | A | FAIL |
|
|
Incomplete coverage at front of store next to entryway, upright head is blocked by a soffit below.
|
FIR05-00518
| INSP-Sprinkler Rough-in | 8/31/2005 | 9/1/2005 | 9/1/2005 3:18:05 PM | A | PART |
|
|
Overhead sprinkler rough-in is okay to cover at hard lid areas.
|
BLD05-01529
| FIRE-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 1:25:16 PM | A | FAIL |
|
|
Provide proper signage above main entry/exit doors, repair emergency light at west corridor, test HVAC duct smoke detectors, manual flush bolts on the three sets of double doors are not allowed.
|
FIR05-00437
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 1:22:11 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
MIS05-00127
| FIR-Final | 8/31/2005 | 9/1/2005 | 9/1/2005 12:17:27 PM | P | PASS |
|
|
Fire life safety finaled.
|
FIR05-00044
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 10:59:17 AM | A | PART |
|
|
Provide permanent dual phone lines or approval letter for temporary lines at job trailer.
|
BLD04-01909
| FIRE-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 10:57:43 AM | A | FAIL |
|
|
Emergency lighting and exit signs in some locations failed to operate, provide building address at Surprise Way, provide covers and keys for knox boxes, install missing door hardware.
|
FIR05-00373
| INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 9:34:49 AM | A | PASS |
|
|
Ceiling tile at the heads, escutcheons, and spare heads in the head box have been installed. Fire sprinkler permit finaled.
|
FIR05-00373
| INSP-Sprinkler Rough-in/Hydro | 8/31/2005 | 9/1/2005 | 9/1/2005 9:31:05 AM | A | PART |
|
|
Overhead rough-in is okay to cover.
|
FIR05-00310
| INSP-Final Inspection | 8/30/2005 | 9/1/2005 | 9/1/2005 12:00:00 AM | P | PASS |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|