Inspections for the day of: Thursday, September 1, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00056 INSP-Final Inspection9/1/20119/1/20119/2/2011 4:43:39 PMPDONE
Inspection completed 9/2.
BLD10-02409 FIRE-Final Inspection9/1/20119/1/20119/1/2011 5:22:09 PMPPASS
Life safety inspection passed. Noted unit address numbers to be posted adjacent to respective front entry doors.
FIR11-00068 INSP-Final Inspection8/30/20119/1/20119/1/2011 4:42:43 PMAPART
Noted items include; two manual pull stations at the 1st floor to be relocated, provide elevator hat flash upon machine room smoke detection, lock at the breaker to the FACP, signage at the door to the panel room, cd settings at the womens RR basement, 1st and 2nd floors to be adjusted, wall mount strobes in the ceiling position at two mens RR, existing knox box is located distant from the new RA. Functional testing for the new voice evac and PA system passed.
BLD11-01206 FIRE-Final Inspection9/1/20119/1/20119/1/2011 4:35:17 PMPPASS
Life safety inspection passed.
FIR11-00267 INSP-Final Inspection8/31/20119/1/20119/1/2011 4:33:05 PMADEFR
scott - please call 45 minutes prior Phone #: ###-####
FIR11-00450 INSP-Sprinkler Rough-in9/1/20119/1/20119/1/2011 4:32:41 PMPPART
Overhead modifications okay for cover at the drop ceilings.
FIR11-00424 INSP-Final Inspection9/1/20119/1/20119/1/2011 4:31:35 PMPPASS
Scope of work completed. Fire sprinkler permit finaled.
FIR11-00397 INSP-Sprinkler Rough-in8/31/20119/1/20119/1/2011 4:30:42 PMAPART
Overhead rough-in okayed. Approval for cover pending cold cavity protection verification.
FIR10-00137 INSP-Final Inspection8/30/20119/1/20119/1/2011 4:28:42 PMAPASS
Noted correction items finished. Fire alarm permit finaled.