Inspections for the day of: Thursday, September 1, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-03092 FIRE-Final Inspection9/1/20169/1/20169/1/2016 2:56:02 PMPCANC
Instructions were to please call ahead, Ted at Phone #: ###-####, attempted to call at 12:45 and I left a message to try and schedule life fire safety inspection. Attempted to call two more times and both calls went to voicemail. Proceeded to next inspections on my schedule, this inspection request is cancelled and a new inspection request will need to be rescheduled for another date.
FIR16-00464 INSP-Sprinkler Rough-in/Hydro9/1/20169/1/20169/1/2016 2:12:06 PMPPASS
Rough to cover inspection complete for underground supply and remote FDC locations, underground supply and remote FDC approved for cover.
FIR16-00289 INSP-Sprinkler Rough-in/Hydro8/31/20169/1/20169/1/2016 2:09:03 PMPFAIL
Contractor did not have overhead fire protection piping ready for hydrostatic test, hydro will need to be rescheduled for overhead fire sprinkler piping.
FIR16-00101 INSP-Sprinkler Rough-in9/1/20169/1/20169/1/2016 12:44:48 PMPFAIL
Fire sprinkler piping throughout multiple rooms had plastic sheeting (Tenting) removed exposing the pipe in the attic space, plastic sheeting will need to be repaired and re-inspected before cover can be approved for level 5.
BLD16-01666 FIRE-Final Inspection9/1/20169/1/20169/1/2016 12:01:16 PMPPASS
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00559 INSP-Final Inspection9/1/20169/1/20169/1/2016 11:57:35 AMPPASS
Final fire alarm inspection passed/complete.
BLD15-02712 FIRE-Final Inspection8/31/20169/1/20169/1/2016 10:40:46 AMAPASS
No fire sprinkler modifications required, no fire alarm modifications required, equipment is unoccupied and located on the roof, fire extinguisher located inside cabinet, final life fire safety inspection passed/complete.
BLD15-02494 FIRE-Final Inspection9/1/20169/1/20169/1/2016 10:20:51 AMPPART
Fire sprinkler inspection complete for city center level 4, fire alarm inspection for city center level 4 complete, fire extinguishers for level 4 city center are in place and will get current inspection tags installed from a licensed contractor. Partial final life fire safety inspection for level 4 complete (city center side of building is complete). Level 4 convention center side will need fire sprinkler, fire alarm and life fire safety inspections performed at a later date.
FIR16-00128 INSP-Final Inspection9/1/20169/1/20169/1/2016 10:14:51 AMAPART
Final fire alarm inspection for level 4 fire of city center side of the building complete, level 4 of the convention center side of fire alarm system will be completed at a later date.
FIR16-00155 INSP-Final Inspection9/1/20169/1/20169/1/2016 10:13:24 AMAPART
Final fire sprinkler inspection for level 4 fire sprinkler system located in city center building complete, convention center side of level 4 will be inspected at a later date.
FIR16-00088 INSP-Sprinkler Rough-in8/30/20169/1/20169/1/2016 10:02:31 AMPPART
Partial rough to cover inspection complete for foverhead fire sprinkler piping located on levels 1, 2 and 3, notated city approved drawings with blue highlighter/red ink overhead fire sprinkler piping approved for cover.
BLD16-01713 FIRE-Final Inspection8/31/20169/1/20169/1/2016 8:53:16 AMAPASS
Fire sprinkler inspection complete, no modifications to fire alarm system, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00390 INSP-Final Inspection9/1/20169/1/20169/1/2016 8:52:07 AMAPASS
Rough to cover inspection complete for level 2, final fire sprinkler inspection complete for levels 1 and 2.