Inspections for the day of: Friday, September 1, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-03099 FIRE-Final Inspection9/1/20179/1/20179/1/2017 2:48:22 PMPPASS
No fire sprinklers, in duct smoke detectors are stand-alone and not monitored, commercial hood fire suppression system has current inspection tags, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD16-02417 FIRE-Final Inspection9/1/20179/1/20179/1/2017 2:19:16 PMPPASS
Fire sprinkler inspection complete (FIR16-00755), final fire alarm inspection complete, kno box will be installed when received, final life fire safety inspection passed/complete.
FIR16-00755 INSP-Final Inspection9/1/20179/1/20179/1/2017 2:16:40 PMPPASS
Final fire sprinkler inspection passed/complete
FIR17-00506 INSP-Final Inspection9/1/20179/1/20179/1/2017 2:16:15 PMPPASS
Final fire alarm inspection passed/complete.
FIR17-00440 INSP-Sprinkler Rough-in9/1/20179/1/20179/1/2017 2:13:53 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
FIR17-00378 INSP-Final Inspection8/31/20179/1/20179/1/2017 11:16:24 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. Final fire sprinkler inspection for area of work complete.
FIR17-00102 INSP-Sprinkler Rough-in/Hydro8/31/20179/1/20179/1/2017 11:12:30 AMACANC
Call point of contact (Brad Westbrook ###-####) twice to try and schedule hydro test, received voicemail both times, left a message both times and did not get a call back, inspection request will need to be rescheduled.
BLD17-02142 FIRE-Final Inspection8/31/20179/1/20179/1/2017 9:22:18 AMADONE
Fire conference complete, modifications will be required to the fire sprinkler system due to ceiling being removed. Exit discharge illumination will be required at both exits. Painted fire sprinkler heads will need to be replaced.