Inspections for the day of: Wednesday, September 10, 2003.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01727 Final9/9/20039/10/20039/10/2003 12:00:00 AMAPASS
CHRIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE03-02122 Final9/9/20039/10/20039/10/2003 12:00:00 AMAPASS
BRAD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE03-02747 Temporary Service9/9/20039/10/20039/10/2003 12:00:00 AMAPART
darryl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
T/S U/G Ok 9/10/2003 11:42:58 AM
ELE03-02421 Rough-In Permanent Service9/9/20039/10/20039/10/2003 12:00:00 AMAFAIL
Please call Heath @###-#### when you are in route to this job. Thanks; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
clearance in front opf main
remove insulataion 9/10/2003 11:20:53 AM
ELE03-02811 Rough-In Permanent Service9/9/20039/10/20039/10/2003 12:00:00 AMAPASS
CLYDE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
P/S O/H R OK 9/10/2003 10:01:35 AM
ELE02-03244 Final9/9/20039/10/20039/10/2003 12:00:00 AMAFAIL
RON ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
\210.8 9/10/2003 1:37:15 PM
ELE03-02813 Electrical Rough-In9/9/20039/10/20039/10/2003 12:00:00 AMAPASS
JOHN; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
ELE03-02553 Electrical Rough-In9/9/20039/10/20039/10/2003 12:00:00 AMAFAIL
Please do inspection by 10:00 am; Phone #: ###-#### Internet Inspection Request from: chris green300.14 Length of Free Conductors at Outlets, Junctions, and Switch Points.
250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes.
(A) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box

314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies.
Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors.

230.28 Service Masts as Supports.
Where a service mast is used for the support of service-drop conductors, it shall be of adequate strength or be supported by braces or guys to withstand safely the strain imposed by the service drop.
Boise City and Idaho Power require support within 30" of a weather head and 2" IMC or RMC when used as a mast for support.

300.4 Protection Against Physical Damage.
Where subject to physical damage, conductors shall be adequately protected.
(D) Cables and Raceways Parallel to Framing Members.

314.17 Conductors Entering Boxes, Conduit Bodies, or Fittings.
Conductors entering boxes, conduit bodies, or fittings shall be protected from abrasion and shall comply with 314.17(A) through (D).
(C) Nonmetallic Boxes and Conduit Bodies. Nonmetallic boxes and conduit bodies shall be suitable for the lowest temperature-rated conductor entering the box. Where nonmetallic boxes and conduit bodies are used with open wiring or concealed knob-
and-tube wiring, the conductors shall enter the box through individual holes. Where flexible tubing is used to enclose the conductors, the tubing shall extend from the last insulating support to not less than 6 mm (1/4 in.) inside the box and beyond any cable clamp. Where nonmetallic-sheathed cable or multiconductor Type UF cable is used, the sheath shall extend not less than 6 mm (1/4 in.) inside the box and beyond any cable clamp. In all instances, all permitted wiring methods shall be secured to the boxes.
9/10/2003 9:10:03 AM
ELE03-02097 Electrical Rough-In9/10/20039/10/20039/10/2003 12:00:00 AMPPART
bob; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
ok for concrete 9/10/2003 3:31:36 PM
ELE03-02818 Conference9/10/20039/10/20039/10/2003 12:00:00 AMPDONE
dan; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE03-02819 Temporary Service9/10/20039/10/20039/10/2003 12:00:00 AMPPASS
john; Phone #: ###-#### Internet Inspection Request from: Darla Downs
T/S U/G Ok 9/10/2003 3:50:14 PM
ELE03-01685 Electrical Rough-In9/10/20039/10/20039/10/2003 12:00:00 AMPNH
ok per jim s to put in for this afternoon