Inspections for the day of: Wednesday, September 10, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00899 INSP-Sprinkler Rough-in/Hydro9/10/20089/10/20089/11/2008 9:36:21 AMPPART
Hydrostatic testing for the new 6" main completed.
FIR08-00539 INSP-Final Inspection9/10/20089/10/20089/10/2008 2:48:08 PMPPASS
Fire sprinkler work passed final inspection, permit scope finaled.
FIR08-00591 INSP-Final Inspection9/10/20089/10/20089/10/2008 2:47:03 PMPPASS
Functional testing of the new duct detector passed field inspection, new panel map provided, fire alarm permit finaled.
BLD08-01879 FIRE-Final Inspection9/10/20089/10/20089/10/2008 2:45:26 PMPPASS
C/N completed, life safety finaled.
BLD08-01576 FIRE-Final Inspection9/9/20089/10/20089/10/2008 11:10:52 AMAPASS
Life safety inspection passed, keyed lock and visual indicator at the main entry/exit door to be complete prior to structural final approval as discussed.
FIR08-00163 INSP-Final Inspection9/9/20089/10/20089/10/2008 11:09:05 AMAPART
Listed correction notice items are complete, overhead work passed inspection, final pending alarm testing for riser flow and tamper switches.
FIR08-00164 INSP-Final Inspection9/9/20089/10/20089/10/2008 11:07:02 AMAPART
Items on correction notice have been verified for completion, permit final pending tamper and alarm device testing.
BLD08-00893 FIRE-Conference9/10/20089/10/20089/10/2008 10:06:39 AMADONE
On site visit regarding project fire life safety requirements, fire code review notes, and details related to fire alarm and sprinkler work.
FIR08-00619 INSP-Final Inspection9/9/20089/10/20089/10/2008 12:00:00 AMPFAIL
Horn/strobes did not function correctly. Strobes were only working
intermittently.When retesting check end of line voltage drop.KR
BLD08-01486 FIRE-Final Inspection9/10/20089/10/20089/10/2008 12:00:00 AMPFAIL
Exit signs at both exits did not function. Exterior egress lights at both exits were not installed. No fire extinguisher was installed.Fire alarm permit needs to be finaled before life safety can be signed off.KR