FIR07-00899
| INSP-Sprinkler Rough-in/Hydro | 9/10/2008 | 9/10/2008 | 9/11/2008 9:36:21 AM | P | PART |
|
|
Hydrostatic testing for the new 6" main completed.
|
FIR08-00539
| INSP-Final Inspection | 9/10/2008 | 9/10/2008 | 9/10/2008 2:48:08 PM | P | PASS |
|
|
Fire sprinkler work passed final inspection, permit scope finaled.
|
FIR08-00591
| INSP-Final Inspection | 9/10/2008 | 9/10/2008 | 9/10/2008 2:47:03 PM | P | PASS |
|
|
Functional testing of the new duct detector passed field inspection, new panel map provided, fire alarm permit finaled.
|
BLD08-01879
| FIRE-Final Inspection | 9/10/2008 | 9/10/2008 | 9/10/2008 2:45:26 PM | P | PASS |
|
|
C/N completed, life safety finaled.
|
BLD08-01576
| FIRE-Final Inspection | 9/9/2008 | 9/10/2008 | 9/10/2008 11:10:52 AM | A | PASS |
|
|
Life safety inspection passed, keyed lock and visual indicator at the main entry/exit door to be complete prior to structural final approval as discussed.
|
FIR08-00163
| INSP-Final Inspection | 9/9/2008 | 9/10/2008 | 9/10/2008 11:09:05 AM | A | PART |
|
|
Listed correction notice items are complete, overhead work passed inspection, final pending alarm testing for riser flow and tamper switches.
|
FIR08-00164
| INSP-Final Inspection | 9/9/2008 | 9/10/2008 | 9/10/2008 11:07:02 AM | A | PART |
|
|
Items on correction notice have been verified for completion, permit final pending tamper and alarm device testing.
|
BLD08-00893
| FIRE-Conference | 9/10/2008 | 9/10/2008 | 9/10/2008 10:06:39 AM | A | DONE |
|
|
On site visit regarding project fire life safety requirements, fire code review notes, and details related to fire alarm and sprinkler work.
|
FIR08-00619
| INSP-Final Inspection | 9/9/2008 | 9/10/2008 | 9/10/2008 12:00:00 AM | P | FAIL |
|
|
Horn/strobes did not function correctly. Strobes were only working
intermittently.When retesting check end of line voltage drop.KR
|
BLD08-01486
| FIRE-Final Inspection | 9/10/2008 | 9/10/2008 | 9/10/2008 12:00:00 AM | P | FAIL |
|
|
Exit signs at both exits did not function. Exterior egress lights at both exits were not installed. No fire extinguisher was installed.Fire alarm permit needs to be finaled before life safety can be signed off.KR
|