Inspections for the day of: Thursday, September 10, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00831 INSP-Sprinkler Rough-in9/10/20099/10/20099/11/2009 7:24:37 AMPPASS
This turned into a conference on what was left to complete on this project.
FIR09-00317 INSP-Sprinkler Rough-in/Hydro9/9/20099/10/20099/10/2009 12:53:42 PMPPASS
Start of 24 hour air test at 12:00. The starting pressures have been written on the wall adjacent to the risers with the current air pressure.
BLD09-00791 FIRE-Final Inspection9/10/20099/10/20099/10/2009 12:52:07 PMAPART
Life safety passed.
FIR09-00317 INSP-Sprinkler Rough-in/Hydro9/9/20099/10/20099/10/2009 12:51:31 PMAPASS
System #2 passed hydrostatic testing.
BLD07-01846 FIRE-Sprinkler Rough-in9/10/20099/10/20099/10/2009 12:50:33 PMPFAIL
The project related fire alarm permit needs addressed prior to life safety. I did have the emergency light in the shower room tested while I was waiting for the fire alarm contractor. Will need to be rescheduled.
FIR08-00382 INSP-Alarm Testing9/10/20099/10/20099/10/2009 12:49:09 PMPFAIL
The fire alarm contractor was not available while I was on site for the inspection. To be rescheduled.
BLD08-02496 FIRE-Final Inspection9/8/20099/10/20099/10/2009 11:12:38 AMAPASS
Life safety passed.
FIR07-01032 INSP-Sprinkler Rough-in9/9/20099/10/20099/10/2009 10:48:11 AMAPASS
See the city approved plans for locations where the piping can be covered.
BLD09-01483 FIRE-Final Inspection9/9/20099/10/20099/10/2009 10:47:31 AMAFAIL
Remove the thumbturn from the main exit. Keyed hardware on the egress side is ok if the sticker is provided. Remove the thumbturn locks on all of the other exterior doors. Provide approved floor plan that matches the actual wall layout.
BLD09-01482 FIRE-Final Inspection9/9/20099/10/20099/10/2009 10:43:39 AMAFAIL
Provide single action hardware on the warehouse door.