BLD10-00664
| FIRE-Final Inspection | 9/10/2010 | 9/10/2010 | 9/10/2010 4:33:06 PM | P | CANC |
|
|
Overbooked
|
FIR10-00355
| INSP-Sprinkler Rough-in/Hydro | 9/9/2010 | 9/10/2010 | 9/10/2010 4:30:05 PM | P | PART |
|
|
Overhead hydrostatic test of the wet system riser adjacent to the dry valve passed.
|
BLD10-01015
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 4:16:36 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD10-01718
| FIRE-Final Inspection | 9/10/2010 | 9/10/2010 | 9/10/2010 3:47:27 PM | P | CANC |
|
|
Overbooked
|
BLD10-01207
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 3:38:53 PM | A | FAIL |
|
|
See fire code review notes items # 5, 6, 11, and 30 for items in need of revision including knox box, address numbers, EM lighting, signage at the riser room door. Replace ceiling at the comm room and provide missing escutcheon.
|
FIR10-00402
| INSP-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 3:36:15 PM | A | PASS |
|
|
Noted corrections verified for compliance. Fire alarm testing passed, permit finaled.
|
BLD10-01588
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 2:35:40 PM | P | CANC |
|
|
Overbooked
|
FIR10-00395
| INSP-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 2:16:50 PM | A | CANC |
|
|
Overbooked
|
BLD10-01693
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 2:13:24 PM | A | PART |
|
|
Phase one temp okay per T. Cobbley.
|
BLD10-01600
| FIRE-Final Inspection | 9/10/2010 | 9/10/2010 | 9/10/2010 1:40:55 PM | P | FAIL |
|
|
Provide approved door hardware at two locations, remove the manual thumbturn at the lower level exit.
|
BLD10-00636
| FIRE-Final Inspection | 9/10/2010 | 9/10/2010 | 9/10/2010 12:51:05 PM | P | FAIL |
|
|
Refer to activity notes for a list deficient items.
|
BLD10-00636
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 12:48:50 PM | A | FAIL |
|
|
Provide missing building address numbers, post signage at the main entry/exit door, project related fire alarm and sprinkler permits need finaled- see correction items regarding fire sprinkler work.
|
FIR10-00338
| INSP-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 12:46:58 PM | A | FAIL |
|
|
SW head at the exterior compressor room appears painted, provide bags at pendent heads in the spray booth per NFPA 13, upright heads within the 7' zone of the unit heaters must be high temperature per fig.8.3.2.5, control valve at supply to booth heads needs to be supervised.
|
BLD10-00924
| FIRE-Conference | 9/9/2010 | 9/10/2010 | 9/10/2010 12:01:08 PM | A | DONE |
|
|
On site conference with contractor regarding fire life safety items including door hardware, exit signs/EM lights, review notes, project related fire alarm work, etc. Missing city approved plan set on site.
|
BLD10-02083
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 11:58:54 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable, door hardware at one location changed while on site, existing sprinkler system is current with annual certification tags.
|
BLD10-01052
| FIRE-Final Inspection | 9/9/2010 | 9/10/2010 | 9/10/2010 11:56:01 AM | A | PASS |
|
|
Fire life safety final approved, project related fire alarm and sprinkler permits are complete.
|
FIR10-00450
| INSP-Sprinkler Rough-in | 9/10/2010 | 9/10/2010 | 9/10/2010 11:48:11 AM | P | PART |
|
|
Overhead fire sprinkler work is approved for cover.
|