Inspections for the day of: Thursday, September 10, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02813 Final9/10/20159/10/20159/10/2015 3:39:09 PMPPASS
Call dave for info Phone #: ###-#### Inspection requested via web by Matt Phillips Rough in consists of cat-6 run through trusses a d above grid to temp sensors through out store. Final ok
ELE15-01111 Electrical Rough-In9/9/20159/10/20159/10/2015 3:04:35 PMPPASS
We need a wall cover inspection for afternoon. Site contact is Mike Poff Phone #: ###-#### Inspection requested via web by Stacie Tasker Discussed the absence of show window receptacle outlets, shall be required as per 210.63. Kitchen area, 1/2 walls, and offices as noted on contractor print wall rough in ok cover
ELE15-02165 Rough-In Permanent Service9/10/20159/10/20159/10/2015 2:20:54 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Main disconnecting means is fused so talked to contractor to make sure available fault current posted by final. Service rough in ok p/s u/g n ok
ELE15-02361 Final9/10/20159/10/20159/10/2015 1:57:07 PMPPASS
Clifton Phone #: ###-#### Final ok
ELE15-02259 Final9/9/20159/10/20159/10/2015 12:59:35 PMPFAIL
Phone #: ###-#### Inspection requested via web by Cyndi Dale 110.24- Available fault current shall be posted in the field. The field markings shall have date fault current calculation was performed. 511.12- All 125 volt 15 and 20 amp receptacle outlets installed where electrical diagnostic equipment, hand tools, or portable lighting are used shall have GFCI protection, including ceiling receptacle outlets.
ELE15-02855 Final9/9/20159/10/20159/10/2015 12:08:43 PMAPASS
Power off for more than 1 year Inspection requested via web by steve ragan Final ok
ELE15-02855 Permanent Service9/10/20159/10/20159/10/2015 12:08:29 PMPPASS
Power off for more than 1 year Inspection requested via web by steve ragan p/s o/h rec ok
ELE15-02598 Electrical Rough-In9/9/20159/10/20159/10/2015 11:03:58 AMAPASS
Ceiling inspection of Customer Service, Cash ; Counting. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Boarders only in storage area, customer service and cash sounting areas rough in ok cover
ELE15-02821 Rough-In Permanent Service9/9/20159/10/20159/10/2015 10:51:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Richard Gratiot Rough in ok cover p/s u/g n ok
ELE15-02210 Final9/8/20159/10/20159/10/2015 10:12:05 AMAPASS
We are requesting a final inspection (auditorium area) for Thursday 9/10/15 in the AM. Our onsite contact is Rich @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate No card posted. Final ok
ELE15-01598 Final9/9/20159/10/20159/10/2015 9:30:22 AMAPASS
Contact Karen at ###-#### for access Phone #: ###-#### Inspection requested via web by steve ragan Final ok
ELE15-02224 Final9/10/20159/10/20159/10/2015 9:07:10 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
ELE15-02857 Rough-In Permanent Service9/8/20159/10/20159/10/2015 8:43:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Will Sevy Rough in ok cover p/s u/g n ok