FIR15-00568
| INSP-Sprinkler Rough-in | 9/9/2015 | 9/10/2015 | 9/10/2015 3:06:03 PM | A | CANC |
|
|
Overbooked. Rescheduled for tomorrow
|
FIR15-00605
| INSP-Final Inspection | 9/10/2015 | 9/10/2015 | 9/10/2015 3:01:14 PM | P | CANC |
|
|
Overbooked will need to be rescheduled. I spoke to the contact
|
BLD15-03126
| FIRE-Final Inspection | 9/9/2015 | 9/10/2015 | 9/10/2015 2:51:29 PM | P | FAIL |
|
|
Repair or remove the exit signs and emergency lights with in the tenant space. Repair the exit signs and emergency lights in the stair well/common path of egress.
|
FIR15-00223
| INSP-Final Inspection | 9/9/2015 | 9/10/2015 | 9/10/2015 2:23:42 PM | P | PASS |
|
|
permit finaled
|
FIR15-00294
| INSP-Final Inspection | 9/9/2015 | 9/10/2015 | 9/10/2015 2:12:34 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00701
| INSP-Final Inspection | 9/8/2015 | 9/10/2015 | 9/10/2015 12:25:23 PM | P | CANC |
|
|
Cancel per John Phone #: ###-####
|
FIR15-00479
| INSP-Sprinkler Rough-in | 9/10/2015 | 9/10/2015 | 9/10/2015 10:56:26 AM | P | CANC |
|
|
Cancel per Leroy. Rescheduled for tomorrow morning.
|
FIR15-00303
| INSP-Sprinkler Rough-in | 9/9/2015 | 9/10/2015 | 9/10/2015 10:51:48 AM | A | PART |
|
|
Rough-in for the overhead piping is passed as far as the installation. I noted two areas of concern which are the hvac unit ducting that penatrates the roof is obstructing the discharge of the ESFR heads in two locations, and the second area of concern is the walkway grating that exceeds 4'-0" in width (grating with accompanying support structure is 4'-5 1/2") with no sprinkler protection provided under it. Two areas have been provided protection but not the entire structure. I also noted that there is no protection under the two stairways to the mezzanine.
|
BLD15-01317
| FIRE-Conference | 9/9/2015 | 9/10/2015 | 9/10/2015 10:38:37 AM | A | DONE |
|
|
Monty Smith discussed the change out of the duct smoke detectors not requiring permits due to being considered a maintenance issue.
|
BLD13-03319
| FIRE-Final Inspection | 9/9/2015 | 9/10/2015 | 9/10/2015 8:19:38 AM | A | PASS |
|
|
Life safety passed
|
FIR15-00297
| INSP-Sprinkler Rough-in | 9/9/2015 | 9/10/2015 | 9/10/2015 8:17:54 AM | A | CANC |
|
|
Wrong permit number scheduled
|
FIR15-00584
| INSP-Final Inspection | 9/8/2015 | 9/10/2015 | 9/10/2015 8:17:00 AM | A | CANC |
|
|
Cancel per Ray McQueen Phone #: ###-####
|