Inspections for the day of: Thursday, September 10, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00568 INSP-Sprinkler Rough-in9/9/20159/10/20159/10/2015 3:06:03 PMACANC
Overbooked. Rescheduled for tomorrow
FIR15-00605 INSP-Final Inspection9/10/20159/10/20159/10/2015 3:01:14 PMPCANC
Overbooked will need to be rescheduled. I spoke to the contact
BLD15-03126 FIRE-Final Inspection9/9/20159/10/20159/10/2015 2:51:29 PMPFAIL
Repair or remove the exit signs and emergency lights with in the tenant space. Repair the exit signs and emergency lights in the stair well/common path of egress.
FIR15-00223 INSP-Final Inspection9/9/20159/10/20159/10/2015 2:23:42 PMPPASS
permit finaled
FIR15-00294 INSP-Final Inspection9/9/20159/10/20159/10/2015 2:12:34 PMPPASS
Permit finaled
FIR14-00701 INSP-Final Inspection9/8/20159/10/20159/10/2015 12:25:23 PMPCANC
Cancel per John Phone #: ###-####
FIR15-00479 INSP-Sprinkler Rough-in9/10/20159/10/20159/10/2015 10:56:26 AMPCANC
Cancel per Leroy. Rescheduled for tomorrow morning.
FIR15-00303 INSP-Sprinkler Rough-in9/9/20159/10/20159/10/2015 10:51:48 AMAPART
Rough-in for the overhead piping is passed as far as the installation. I noted two areas of concern which are the hvac unit ducting that penatrates the roof is obstructing the discharge of the ESFR heads in two locations, and the second area of concern is the walkway grating that exceeds 4'-0" in width (grating with accompanying support structure is 4'-5 1/2") with no sprinkler protection provided under it. Two areas have been provided protection but not the entire structure. I also noted that there is no protection under the two stairways to the mezzanine.
BLD15-01317 FIRE-Conference9/9/20159/10/20159/10/2015 10:38:37 AMADONE
Monty Smith discussed the change out of the duct smoke detectors not requiring permits due to being considered a maintenance issue.
BLD13-03319 FIRE-Final Inspection9/9/20159/10/20159/10/2015 8:19:38 AMAPASS
Life safety passed
FIR15-00297 INSP-Sprinkler Rough-in9/9/20159/10/20159/10/2015 8:17:54 AMACANC
Wrong permit number scheduled
FIR15-00584 INSP-Final Inspection9/8/20159/10/20159/10/2015 8:17:00 AMACANC
Cancel per Ray McQueen Phone #: ###-####