FIR19-00333
| INSP-Sprinkler Rough-in | 9/10/2019 | 9/10/2019 | 9/10/2019 3:04:14 PM | P | PASS |
|
|
Rough to cover inspection for underground supply complete, approved for cover.
WILL CALL WHEN CLOSE TO DONE. Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 9/9/2019 | 9/10/2019 | 9/10/2019 1:38:01 PM | P | CANC |
|
|
Sprinkler design has been resubmitted for piping changes, hydro will not be completed until plans are re-issued and pipe changes are accepted without any other modification requirements, this request is cancelled.
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00506
| INSP-Sprinkler Rough-in/Hydro | 9/9/2019 | 9/10/2019 | 9/10/2019 1:34:44 PM | P | FAIL |
|
|
Tenting not installed correclty in numerous areas, cover is not approved, hydro to be completed after vertical section of pipe in attic space is moved closer to sheetrock for freeze prevention.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-01199
| FIRE-Final Inspection | 9/9/2019 | 9/10/2019 | 9/10/2019 10:29:14 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishert is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Kendall Phone #: ###-####
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 9/9/2019 | 9/10/2019 | 9/9/2019 9:53:34 AM | A | CANC |
|
|
Request was for a conference, this request is cancelled per conversation with point of contact.
Robert Chambers is the contact. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|