BLD02-01670
| FIRE-Final Inspection | 9/11/2002 | 9/11/2002 | 9/11/2002 12:00:00 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 09/11/2002 at 07:21:38. Contact: ###-####. fire not required for sign off 9/11/2002 7:59:09 AM
|
BLD02-01263
| FIRE-Final Inspection | 9/11/2002 | 9/11/2002 | 9/11/2002 12:00:00 AM | P | PART |
|
|
temp occ -david; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie approved by Dave Miller for temp occ pending completion of fire alarm permit for duct detectors for AHU shutdown 9/11/2002 4:08:28 PM
|
BLD02-01534
| FIRE-Final Inspection | 9/11/2002 | 9/11/2002 | 9/11/2002 12:00:00 AM | P | PASS |
|
|
todd--ceiling grid; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie fire extinguisher will be hung by back door; structural please verify 9/11/2002 2:51:02 PM
|
BLD02-01583
| FIRE-Final Inspection | 9/10/2002 | 9/11/2002 | 9/11/2002 12:00:00 AM | P | PASS |
|
|
KAREN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR01-00437
| INSP-Final Inspection | 9/10/2002 | 9/11/2002 | 9/11/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 09/10/2002 at 18:12:40. Contact: ###-####. 4 horn circuits shown on plans - 3 installed need to verify voltage drops and locations of EOL's; need supervised ball valve switch for dry system alarm switch; labels not fixed for tampers 9/11/2002 2:40:10 PM
|