Inspections for the day of: Thursday, September 11, 2003.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00069 INSP-Supply line flush9/10/20039/11/20039/11/2003 12:00:00 AMANR
Scheduled by a contractor via Hello! on 9/10/2003 at 8:30:20 AM. Contact: ###-####. will reschedule 9/11/2003 12:27:08 PM
FIR03-00136 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:32:06 AM. Contact: ###-####. . okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:33:32 PM
FIR03-00135 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:34:36 AM. Contact: ###-####. . okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:33:47 PM
FIR03-00115 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:35:43 AM. Contact: ###-####. okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:33:58 PM
FIR03-00138 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:36:47 AM. Contact: ###-####. okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:34:08 PM
FIR03-00137 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:38:12 AM. Contact: ###-####. okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:34:23 PM
FIR03-00139 INSP-Sprinkler Rough-in/Hydro9/10/20039/11/20039/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 9/10/2003 at 8:39:36 AM. Contact: ###-####. okay to cover rooms; corridor requires firestopping; standpipes over 48 inches high 9/11/2003 12:33:14 PM
BLD02-02583 FIRE-Final Inspection9/10/20039/11/20039/11/2003 12:00:00 AMAFAIL
mike; Phone #: ###-#### Internet Inspection Request from: Annette Moore alarms not interconnected to main hospital; standpipe connections higher than 48 inches 9/11/2003 9:51:27 AM
BLD03-01091 FIRE-Final Inspection9/10/20039/11/20039/11/2003 12:00:00 AMAPART
jake; Phone #: ###-#### Internet Inspection Request from: Annette Moore phasing this permit and will complete the other restrooms; okay to occupy the offices; door hardware on exit doors and restroom door to be openable from the inside without special knowledge 9/11/2003 8:16:32 AM
FIR03-00292 INSP-Final Inspection9/10/20039/11/20039/11/2003 12:00:00 AMACANC
please do not not arrive untill after 11:00AM. Thanks Trent; Phone #: ###-#### Internet Inspection Request from: Trent Bice inspection not needed at this time as alarms aren't ready 9/11/2003 11:50:33 AM
BLD03-00926 FIRE-Supply Line Hydro9/11/20039/11/20039/11/2003 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 9/11/2003 at 7:14:23 AM. Contact: ###-####. fire not required - wrong type inspection called in 9/11/2003 10:57:19 AM
FIR03-00347 INSP-Sprinkler Rough-in/Hydro9/11/20039/11/20039/11/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 9/11/2003 at 8:45:47 AM. Contact: ###-####. tenting has started and the areas started are going good; middle area of south side okay for rough-in 9/11/2003 2:25:24 PM
BLD03-01640 FIRE-Final Inspection9/11/20039/11/20039/11/2003 12:00:00 AMPFAIL
tim; Phone #: ###-#### Internet Inspection Request from: Darla Downs sprinkler monitoring panel requires smoke detector above panel, manual pull and audible alarm; 9/11/2003 1:44:47 PM
FIR03-00473 INSP-Final Inspection9/11/20039/11/20039/11/2003 12:00:00 AMPPASS
FIR03-00310 INSP-Final Inspection9/9/20039/11/20039/11/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 9/9/2003 at 12:14:25 PM. need duct detector zone to report supervisory, not trouble; need updated map and as builts 9/11/2003 4:46:23 PM
FIR03-00113 INSP-Final Inspection9/10/20039/11/20039/11/2003 12:00:00 AMPPASS
dan ###-####