FIR06-00407
| INSP-Final Inspection | 9/11/2006 | 9/11/2006 | 9/11/2006 4:07:52 PM | P | NR |
|
|
Project is not complete for final, rough-in inspection failed.
|
FIR05-00272
| INSP-Sprinkler Rough-in/Hydro | 9/8/2006 | 9/11/2006 | 9/11/2006 4:06:47 PM | P | PART |
|
|
AG hydrostatic test passed.
|
FIR06-00407
| INSP-Sprinkler Rough-in | 9/11/2006 | 9/11/2006 | 9/11/2006 3:16:35 PM | P | FAIL |
|
|
One head is blocked by a light fixture in the NE hallway, heads are overspaced in the north hall at two locations, work room head is overspaced off one adjacent wall, overspacing at the west side of the teller area, inspection concluded at this time due to the number of defficiencies-east side of the TI area not inspected today.
|
FIR06-00347
| INSP-Final Inspection | 9/8/2006 | 9/11/2006 | 9/11/2006 3:11:18 PM | A | PASS |
|
|
Final fire alarm inspection passed.
|
FIR06-00349
| INSP-Final Inspection | 9/8/2006 | 9/11/2006 | 9/11/2006 3:10:48 PM | A | PASS |
|
|
Fire alarm work passed inspection.
|
FIR05-00403
| INSP-Sprinkler Rough-in | 9/8/2006 | 9/11/2006 | 9/11/2006 10:25:10 AM | A | PART |
|
|
OH rough-in is good for cover on the first and second floors only, third floor will require a tenting inspection prior to cover.
|
MIS06-00229
| FIR-Final | 9/5/2006 | 9/11/2006 | 9/11/2006 10:20:20 AM | A | PASS |
|
|
Life safety passed inspection.
|