Inspections for the day of: Tuesday, September 11, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03549 Permanent Service9/10/20079/11/20079/11/2007 3:32:10 PMPPASS
james Phone #: ###-#### p/s u/g rec ok
ELE07-03152 Final9/11/20079/11/20079/11/2007 2:45:59 PMPCANC
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr, wrong type inspection, told contractor had to be ri 1st, see ri since it failed
ELE07-03152 Electrical Rough-In9/11/20079/11/20079/11/2007 2:29:40 PMPFAIL
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr ,gave verbal corr notice,nec 300.11(A) no wiring shall be supported on grid or tiles, 725.3(B) abandoned low voltage wiring shall be removed, BCC shall provide seismic support wires, no tiles shall be installed, no violations shall be retained
ELE07-01624 Electrical Rough-In9/11/20079/11/20079/11/2007 2:21:06 PMPPART
Scheduled by a contractor via Hello! on 9/11/2007 at 10:52:58 AM. Contact: ###-####. walls anop ok to cover
ELE07-02544 Electrical Rough-In9/11/20079/11/20079/11/2007 1:50:57 PMPFAIL
Scheduled by a contractor via Hello! on 9/11/2007 at 10:45:42 AM. Contact: ###-####. met contr, left corr notice, BCC no ceiling tiles shall be installed before inspection
ELE07-02633 Final9/11/20079/11/20079/11/2007 12:52:29 PMPPASS
larry Phone #: ###-#### ok to final
ELE07-03144 Electrical Rough-In9/10/20079/11/20079/11/2007 11:49:30 AMAPASS
###-#### brian walls only ok to cover
ELE07-02876 Electrical Rough-In9/10/20079/11/20079/11/2007 10:35:50 AMANR
EQUIPOTENTIAL GRID Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called, not done with rebar yet, fee due
ELE07-02775 Permanent Service9/11/20079/11/20079/11/2007 10:06:46 AMAPASS
corrections made, need to verify at final that water pipe has been changed to plastic or inspector reserves the right to turn off power. Contractor states that 3/4" exst water pipe is too small and will be changing to larger size. p/s u/g rec ok
ELE07-02237 Permanent Service9/10/20079/11/20079/11/2007 10:02:24 AMACANC
jack Phone #: ###-#### wrong permit and address,see added inspection for next door ( ele07-02775)
ELE07-02124 Final9/10/20079/11/20079/11/2007 9:46:50 AMAPASS
Final on shell with house panel, exterior entry lighting, and exits where we would not have access on TI Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-00746 Final9/10/20079/11/20079/11/2007 9:21:59 AMAPASS
Final for shell, house panel, entry and exterior lighing with exits installed where we would not have access to on the TI Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-01060 Final9/10/20079/11/20079/11/2007 8:57:15 AMAPASS
Final for shell, with house panel, exterior entry lighting, and exits where we would not have access on TI Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-01398 Final9/10/20079/11/20079/11/2007 8:06:05 AMAPASS
Final for shell, house panel, exterior entry lighting, and exits where we would not have access on TI Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-01814 Final9/10/20079/11/20079/11/2007 7:49:44 AMAPASS
Final shell, house panel, exterior entry lighting, and exits where we would not have access to on TI Phone #: ###-#### Internet Inspection Request from: Brad Baker ok to final
ELE07-02302 Electrical Rough-In9/10/20079/11/20079/10/2007 10:46:31 AMPCANC
Contact: Steve Hess - U/G inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden